Troubleshooting 129
5.2.25 777Error
Error conditions and Check Items
Is the factory jumper
installed properly
on CN24?
Is the LWCO
installed properly?
Is the output
voltage normal on
CN25? (AC 24V)
Is proper power being
supplied to the LWCO?
Replace the main PCB
Check LWCO
Check the factory
installed jumper
and jumper
connection (CN24)
Check the
connecting
terminals
(CN25)
No
No
Yes
No
Yes
Yes
Yes
Check method
Fault
Possible Causes
Check method
E777
Abnormal factory
installed jumper
1. Check the factory installed jumper and jumper connection.
2. Check the output voltage normal.
Check the output voltage ( Normal voltage : AC 24V)
Содержание NCB-150E