Troubleshooting 97
5.2.4 012Error
Error occurrence conditions and check items
Error
Description
E012
Flame loss
If the system detects loss of flame during combustion, the system stops supplying fuel,
attempts to restart, counts the incidents of flame loss, and if the incident occurs 20 times
consecutively displays 012E (manually cleared) on the front panel.
Check items
1. Measure, with a manometer the gas supply pressure (NG: 3.5" - 10.5” W.C, LP: 8”- 13.5" W.C)
2. Check the Gas meter Capacity.
3. Tighten the ground connection screws on heat exchanger.
4. Check if the gas orifice is clogged.
5. Check if the PCB is working properly.
Does the boiler have
sufficient gas pressure?
Check connector
(#1 of CON22)
see page 18 for Wiring Diagram
Check the gas pressure
Gas Pressure
Natural Gas: 3.5” - 10.5” W.C.
LP Gas: 8.0" - 13.5" W.C.
No
Yes
* Check the flame detection AD value for
proper resistance. (refer to page 42-43)