System Details 55
Component
Test Performed
Display Method
Fan
Gradually increase / decrease the speed of
the fan motor starting from 0 RPM to full
speed and back down to 0 RPM
The current APS value and the current RPM value are repeatedly
displayed at intervals of 2 seconds.
Pump
Cycles the pump 10 seconds ON and 5
seconds OFF five times. (Repeats five times
for a total of 75 seconds)
Displays On or Off according to pump status.
3-Way Valve
3-Way Valve will be turned On upon entering
<Test mode> and pressing the [+], [-] button
each time converts the state from On -> Off
or Off -> On
Whenever the [+], [-] button is pressed, the condition is toggled as
On -> Off or Off -> On
Dual Venturi
Dual Venturi will be turned On upon entering
<Test mode> and pressing the [+], [-] button
each time converts the state from On -> Off
or Off -> On
Whenever the [+], [-] button is pressed, the condition is toggled as
On -> Off or Off -> On
* Error Check Operation will return to Normal Operation condition after automatic test when selecting each operation mode (3-Way Valve and Dual Venturi will
be manually controlled)