Version 1.4
72 NCB-E Service Manual
4.9.9 Burner
Part
Check Point
Function
1. Pre-Mix system reduces emissions and increase efficiency.
2. The burner facilitates the air/gas mixture necessary to produce the proper heat during
combustion.
Failure Event
1. Unable to initialize/sustain combustion.
2. Dust or soot deposit on the burner surface
3. Possible gas leakage from burners.
Effects
1. Abnormal combustion.
2. Unstable flame conditions and/or flame loss.
3. Ignition failure.
Error Code
E003, E004, E012
Diagnostic
Visual inspection: Excessive deposits on the burner surface and/or unstable flame conditions
during operation.
Fuel Gas Supply
Combustion Air Supply
Burner Body
(Fuel Gas +
Combustion Air Mix Zone)
Содержание NCB-150E