88 NCB-E Service Manual
Failure mode
Cause
Check method
Other trouble
Capacity setting
Sudden increase of temperature due to PCB DIP S/W model setting error or max setting.
Capacity
DIP S/W No.
5
6
150,000 BTU (180)
OFF
OFF
175,000 BTU (210)
ON
OFF
199,000 BTU (240)
OFF
ON
120,000 BTU (150)
ON
ON
Defective PCB
If the trouble continues despite the checking of above items, replace the PCB.