finish framing - after appliance installation
11.0 minimum combustible mantel clearances
Installing a mantel between this appliance and
electronics or other materials that may be sensitive
to heat, will reduce the effect of direct heat on them.
Follow mantel height and depth instructions for proper
clearance information. A non-combustible mantel is
considered a non-combustible protrusion
Electronics, picture frames, decors, or other wall-
mounted objects must be 6” below the air outlet
opening and 6” above the finishing flange.
E
D C B
A
A
Top of
finishing
flange
Bottom of
the unit
25 11/16" (65.2cm)
2" (5.1cm)
2" (5.1cm)
12" (30.5cm)
MANTEL HEIGHT
MANTEL DEPTH
Bottom of
finishing flange
Optional hearth
extension
• Risk of fire. Maintain all specified air space clearances to combustibles. Failure to comply with these
instructions may cause a fire or cause the appliance to overheat. Ensure all clearances (i.e. back, side, top,
vent, mantel, front, etc.) are clearly maintained.
• When using paint or lacquer to finish the mantel, the paint or lacquer must be heat resistant to prevent
discolouration.
• Installing a television or other electronics above the appliance may cause discolouration, melting, or damage
to the electronics. Use clearances as guidelines and refer to your TV manufacturer’s instructions for further
information.
!
WARNING
6” min.
6” min.
Ceiling
Air outlet opening