EN
W415-1739 / C / 08.03.17
5
installation planning
2.1 installation option 1 - open enclosure (enclosure stops short of the ceiling)
2.2 installation option 2 - front opening
NOT Suitable for Dynamic Heat Control™ Plus
Suitable for Dynamic Heat Control™ Plus
ceiling
2-4”
6” min
DYNAMIC HEAT
CONTROL™ AIR
OUTLET OPEN-
ING IS HOT WHEN
APPLIANCE IS
OPERATING!
Air outlet opening
must
be located out of reach of
the user. Air outlet
must
not be
restricted by furnishings or decor.
RECOMMENDED
Wall mounted
object (picture
frame, appli-
ance, etc.)
It is one option not to finish or close in the top of the enclosure to provide the necessary air circulation path for the
Dynamic Heat Control™
system. Leaving a complete air outlet opening above the enclosure has been found to
be well accepted with respect to final appearance and offer minimal distraction. It also allows for efficient circulation
of air within the room. This option offers the simplest method for framing and installation. (If installing
Dynamic Heat
Control™
Plus
, refer to option 2 or 3 -
DHC Plus cannot be used with option 1
). Limit the air outlet opening
height to 4” to reduce the risk of items inadvertly falling into the enclosure.
The air outlet opening must extend
around the entire perimeter, or the entire front face of the enclosure, where the enclosure runs from wall
to wall.
MINIMUM AIR OUTLET OPENING DIMENSIONS
LVX38
LVX50
LVX62
LVX74
(Q x R)*
80 sq. in. minimum (Q
must
be 2-3”)
160 sq. in. minimum (Q
must
be 2-3”)
S
This dimension is determined from the enclosure height (L) minus the distance to the top of the Dynamic
Heat Control™ air outlet opening (0”-1.5”), height of the air opening (2”-3”), and the distance from the
base of the appliance to the top of the appliance viewing area (25 11/16”).
*Free area. Any trim edging or finishing must not reduce or restrict minimum area. Grills, grates, louvres, or
other unapproved covers are not permitted and will cause a fire hazard.
Wall mounted
object (picture
frame, appli-
ance, etc.)
ceiling
enclosure top
must
be installed
2-3”
0-1.5” Max
6” min
Air outlet opening is required to be centered with the appliance.
ALTERNATIVE
(Q x R)*
DYNAMIC HEAT
CONTROL™ AIR
OUTLET OPEN-
ING IS HOT WHEN
APPLIANCE IS
OPERATING!
Front air outlet opening
must
be located out of reach of the
user. Air outlet
must
not be
restricted by furnishings or
decor.
Minimum air outlet opening dimensions
must
be followed. The opening is required to be framed no more than 1.5” below the
enclosure top (see option 2 diagram) to avoid trapping heat in the upper areas and the air outlet opening centered on the appliance
center.
Framing the air outlet opening lower will overheat the appliance, the enclosure, and finishing material.
S
L
2 1/2”
min