5.2 Wiring of Power Supply
5 - 11
5.2.2
Grounding
Under normal conditions, the inherent noise resistance is sufficient. However, in
situations of excess noise, ground the instrument to increase noise suppression.
For grounding purposes, use wiring with a
minimum of 2 mm
2
. The grounding
connection should have a resistance of
less than 100
Ω
.
The point of grounding should be as close to the PLC unit as possible. The ground wire
should be as short as possible.
If two devices share a single ground point, it may produce an adverse effect. Always
use an exclusive ground for each device.
Other device
(Inverter etc.)
CORRECT
INCORRECT
Other device
(Inverter etc.)
Figure 37: FP
Σ
Grounding
Note
Depending on the surroundings in which the equipment is used,
grounding may cause problems.
Example:
Since the power supply line of the FP
Σ
power supply connector
is connected to the function earth through a varistor, if there is
an irregular potential between the power supply line and earth,
the varistor may be shorted.
24 V DC
0V
Function
earth
Varistor
FP
Σ
power supply line
24 V DC
0V
Function
earth
Varistor
(39 V)
FP0 exponsion unit
power supply line
82 V: for C32T, C32T2
56 V: for C24R2
Figure 38: Power supply line of FP
Σ
and FP0 expansion unit
Содержание FP Series
Страница 15: ...FP Functions and Restrictions of the Unit 1 2...
Страница 25: ...FP Specifications and Functions of Control Unit 2 2...
Страница 37: ...FP Expansion 3 2...
Страница 44: ...Chapter 4 I O Allocation 4 1 I O Allocation 4 3...
Страница 45: ...FP I O Allocation 4 2...
Страница 51: ...FP Installation and Wiring 5 2...
Страница 77: ...FP High speed Counter and Pulse Output Functions 6 2...
Страница 133: ...FP High speed Counter and Pulse Output Functions 6 58...
Страница 135: ...FP Communication Cassette 7 2...
Страница 147: ...FP Communication Function 1 Computer Link 8 2...
Страница 169: ...FP Communication Function 2 General purpose Serial Communication 9 2...
Страница 205: ...FP Communication Function 2 General purpose Serial Communication 9 38...
Страница 207: ...FP Communication Function 3 PLC Link Function 10 2...
Страница 232: ...Chapter 11 Other Functions 11 1 Analog Potentiometer 11 3 11 2 Clock Calendar Function 11 4...
Страница 233: ...FP Other Functions 11 2...
Страница 238: ...Chapter 12 Self Diagnostic and Troubleshooting 12 1 Self Diagnostic Function 12 3 12 2 Troubleshooting 12 5...
Страница 239: ...FP Self Diagnostic and Troubleshooting 12 2...
Страница 249: ...FP Self Diagnostic and Troubleshooting 12 12...
Страница 251: ...FP Specifications 13 2...
Страница 323: ...Index FP I 4...
Страница 325: ...FP Record of changes R 2...