GT20 Control Wiring and Programming Manual
Part #C-00140
Rev. 10-7-16
10-42
Troubleshooting
No
u
Description
Cause
Elimination
Checking Time
Reaction
E4 01 Reference
Switch
Range of Operator
detected in the Open
Position
X
Check:
y
The Connection
y
Switching Point of the
Reference Switch
X
Reference Switch must be
activated in Close position
(Switching Contact open)
Open Position
F
02
Not detected in the
Closed Position
Prior to the First
Setup Run
A
03
Not detected in the
Closed Position
04
Not detected in the
Open Position in
"INVERS" mode
X
Before Start (Teach) door
must be in Open position
X
Reference Switch must be
activated in Open position
(Switching Contact open)
E5 00 Power
Limitation
Control Overload
X
Check/Correct
y
Friction of the Door Panel
y
Pre-Load of Closing Spring
X
Ensure maximum door
weight is not exceeded
Permanent
A
Maximum Power is
Restricted
Table 10-2
Operating
No
Description
Cause
Elimination
Checking Time
Reaction
E10 01 Fullteach
required
Parameter Ao, Rod,
Invers or dAxis changed
X
Carry out a learn cycle Upon changing
the drive unit
configuration
H
02
Minimum opening angle
has not been achieved
X
Check the locking/
electric lock
During Teach
H
E11 01 Halfteach
required
(Opening)
Parameter Vo changed
X
Carry out a complete
and unhindered
opening cycle
Upon changing
the speed
parameters
W
02 Halfteach
required
(Closing)
Parameter Vc or FSlam
changed
X
Carry out a complete
and unhindered
closing cycle
E14 01 Locking/Elecric
Lock
The Door panel got
caught in the locking/
electric lock
Check the function of the
locking/electric lock
When opening
from a closed
position
H
02
The inverted operation
has no locking, or the
interlocking force Fch has
not been programmed
Program/increase the
interlocking force Fch
At the end of the
teach procedure
W
E15 01 Obstacle during
opening
Too many successive
obstacles have occured
X
Examine the
installation
X
Remove the obstacle
X
Move the Door panel
to the target position
Permanent
H, A
Restart after
60’s
02 Obstacle during
closing
E16 01 Temperature
Temperature on output
level has reached 178° F
X
Allow the unit to cool
down
Permanent
A
Drive unit
functions with
reduced power
02
Temperature on output
level has reached 196° F
A
Drive unit
has stopped