GT20 Control Wiring and Programming Manual
Programming 7-29
Table 7-6
Parameter Menu: Settings for Door Panel Movement
Element
Unit Type Default
Value
Description
Region
BOTH
EU
Eu or US EU - Europe; US - United States
Software version determined by UL Standards.
Vo
Full Power
6
0..14
Opening speed (velocity open)
Low Energy
9
0...9
Vc
Full Power
4
0..14
Closing speed (velocity closed)
Low Energy
9
0...9
TOEx Full Power
3s
0...60s TOEx sets the hold-open time resulting from activation signals from
devices connected to: terminals 9+10 for exterior activation and
terminals 12+13 for interior activation.
Low Energy
3s
3...60s
ANSI 156.19 for Low Energy:
TOEx must be no less than 5s.
TKey Full Power
5s
0...180s
X
TKey sets the hold-open time resulting from an activation signal
from a device (referred to as KEY) on terminals 2+3.
X
With TOEx and TKey, you can set a different hold open times for
different activation devices by using different terminals.
Low Energy
5s
3...180s
TPuGo Full Power
3s
0...180s Determines how long the Door Panel stays open.
Low Energy
3s
3...180s
TDelay Full & Low
0.2s
0.0...4.0s Tdelay sets the amount of time the door hesitates to allow the lock to
release before opening.
FDelay Full Power
OFF
OFF...7.0A Fdelay is a temporary “hold closed” force applied to the door to keep it
closed while the electric lock is being released. This parameter sets the
amount of force that is applied. FDelay is only active if TDelay setting is
greater than 0.
Low Energy
OFF
OFF...7.0A
TLock Full & Low
0.5s
0.0...4.0s Sets amount of time Door Panel will press against lock to engage it.
FLock Full & Low
2.0A
OFF...7.0A Sets amount of force that is applied to the door to engage the lock at
the closed position. It is only active if TLock setting is greater than 0.
FSlam Full & Low
OFF
OFF...10 Accelerating function (force slam). For example: When a door panel
needs to be forced shut due to a latch or heavy seals.
FWind Full & Low
OFF
OFF
X
Obstacle detection optimized for exterior doors (wind loads).
X
Assuming that a gust of wind is not a hard obstacle which will
stop the door, the motor current will rise “slowly”. In this case the
GT20 Control will provide additional power to continue the door
movement.
X
When FWind is turned ON, Nabco strongly recommends the use of
door mounted sensors to stop or re-open the door if an obstacle is
detected during the door cycle.
OPEN
CLOSE
BOTH
Fo
Full Power
4
0...9
X
Opening force (force open) when an obstacle is detected during
Open/Close cycle or both.
X
In standard mode Obstacle Detection can not be switched On/Off. It
can be adjusted with parameters “Fo” = Opening force (force open)
and v “Fc” = close force (force close). To make Obstacle Detection
least sensitive: set both parameters on max. (= step 9). To make
Obstacle Detection most sensitive: set both parameters on min. = 0
(caution this can allow the drive to react to small changes in wind).
Low Energy
9
0...9
Fc
Full Power
4
0...9
Low Energy
9
0...9
Foh
Full & Low
4
0...9
Hold-open force (force open hold)
Fch
Full & Low
0.0A
0.0A...3.5A
X
Interlocking Force (force close hold): automatically programs FLock
and FDelay if these settings are set at 0.
X
If there is no electric lock and the Interlocking Force Fch is not
adjusted, Error 14/02 will be displayed as a warning after the
Teach1 procedure and the Door Panel will endlessly re-open.