8
iVector S2
Installation manual
iVector S2 • 2022-07-01
US
1.5 Dimensions
37.5 (1-1/2)
80 (3-5/32)
131 (5-5/32)
579 (22
-3/
4)
449 (17
-11/16)
206 (
8-
1/8
)
102 (
4)
83 (3-1/4)
G3/4"EK
G3/4"EK
A
a1
a2
∅ 14 (1/2)
iVector S2 / Vido S2
2 PIPES – VS
Dimensions
Model
VS 7-2P
VS 9-2P
VS 11-2P
VS 13-2P
VS 15-2P
A
mm
735
935
1135
1335
1535
a1
mm
210
310
410
510
610
a2
mm
254
354
454
554
654
126 (4-15/16)
A
73.5 (2-9/16)
73.5 (2-9/16)
18.5 (3/4)
468.5 (18-
7/16)
228 (
9)
G3/
4“EK
180.5 (7
-3/32)
14 (1/2)
99.5
(3-
15/16
)
G3/
4“EK
194.5 (7
-5/8
)
316 (12
-7
/16)
65.5 (2-9/16)
576 (22
-21/32)
14 (1/2)
468.5 (18-
7/16)
228 (
9)
79.5 (3-1/8)
37.5 (1-1/2)
∅ 14 (1/2)
83.2 (3-9/32)
116 (4-9/16)
83.5 (3-9/32)
4 PIPES
Technical Data (DC)
Model VS
VS 7-4P
VS 9-4P
VS 11-4P
VS 13-4P
VS 15-4P
Model VSI
VSI 7-4P
VSI 9-4P
VSI 11-4P
VSI 13-4P
VSI 15-4P
Length VS
mm (inch)
735 (29)
935 (37)
1135 (45)
1335 (53)
1535 (61)
Length VSI
mm (inch)
378 (15)
578 (23)
778 (31)
978 (39)
1178 (47)
Cooling coil water content
L (US Gal)
0.47 (0.12)
0.8 (0.21)
1.13 (0.30)
1.46 (0.39)
1.8 (0.48)
Heating coil water content
L (US Gal)
0.16 (0.04)
0.27 (0.07)
0.38 (0.10)
0.49 (0.13)
0.6 (0.16)
Maximum working pressure
bar (psi)
10 (145)
10 (145)
10 (145)
10 (145)
10 (145)
Maximum inlet water temperature
°C (°F)
82 (180)
82 (180)
82 (180)
82 (180)
82 (180)
Minimum inlet water temperature
°C (°F)
4 (39)
4 (39)
4 (39)
4 (39)
4 (39)
Water connections
Eurocone 3/4" Eurocone 3/4" Eurocone 3/4" Eurocone 3/4" Eurocone 3/4"
Power supply
V/ph/Hz
120/1/60
120/1/60
120/1/60
120/1/60
120/1/60
Maximum current
A
0.22
0.32
0.36
0.52
0.56
Maximum power
W
11
19
20
29
33
Weight VS
kg (lbs)
18 (40)
21 (47)
25 (55)
28 (62)
32 (71)
Weight VSI
kg (lbs)
10 (22)
13 (29)
17 (38)
20 (44)
24 (53)
2 PIPES – VS
Dimensions
Model
VS 7-2P
VS 9-2P
VS 11-2P
VS 13-2P
VS 15-2P
A
mm (inch)
735 (29)
935 (37)
1135 (45)
1335 (53)
1535 (61)
a1
mm (inch)
210 (9)
310 (13)
410 (17)
510 (20)
610 (24)
a2
mm (inch)
254 (10)
354 (14)
454 (18)
554 (22)
654 (26)
2 PIPES – VSI
Dimensions
Model
VSI 7-2P
VSI 9-2P
VSI 11-2P
VSI 13-2P
VSI 15-2P
A
mm (inch)
378 (14-7/8)
578 (22-3/4)
778 (30-5/8)
978 (38-1/2)
1178 (46-3/8)
2-pipe inset unit shown without factory-fitted valves. For more details see section 4 below.
IP units are converted from SI equivalent – all IP units nominal
Содержание iVector S2
Страница 1: ...Installation manual iVector S2 2022 07 01 US...
Страница 2: ......
Страница 38: ...38 iVector S2 Installation manual iVector S2 2022 07 01 US...
Страница 39: ......