iVector S2
Installation manual
iVector S2 • 2022-07-01
US
1.2 General information
Before proceeding with the installation, unpack the
product and make sure that all the components are
present, and that there is no concealed shipping damage.
Components include:
• unit
• instruction manual
• template
• accessories/mounting kit
This appliance has been designed both for heating and /
or cooling applications and must be installed for this use
only. The installation must take into consideration stated
performance characteristics.
Check the location where the product is to be installed, the
surface must be flat and the specified product clearances
available. If fitted to a wood framed construction, there
may be an adverse effect on sound levels especially
at higher fan speeds. If the product is to be used for
cooling applications, the disposal of condensate must be
considered.
If the appliance is not used for a long period
of time, it is recommended that the product is
electrically isolated, and the connecting valves are
closed. Frost prevention measures must be taken
including use of anti-freeze if appropiate.
Avoid prolonged physical contact with the direct
air flow.
Do not leave the room closed for long periods.
Periodically open the windows to ensure fresh air
exchange.
In the event of a water leak, isolate the electrical supply
and close connecting valves. Contact the installer.
The manufacturer accepts no responsibility, either
contractual or for consequential loss, for any damage
caused to persons, animals of property as a result of
incorrect installation, alteration, maintenance or improper
use.
To ensure that the installation is carried out correctly and
that the unit will perform as designed, carefully follow the
instructions in this manual. Failure to follow the instructions
can not only cause malfunctions of the appliance but
will also invalidate the warranty and hence PG shall not
respond for any damage to persons, animals or property.
All IP units contained in this document are converted from
SI equivalent – all IP units nominal.
1.3 Product range
The iVector S2 is available with casing (VS model) or
without casing (VSI model), in 5 different lengths.
VS models
can be mounted vertically on the wall or
horizontally on the ceiling, with the option for integral
controls (not ceiling), remote mounted controls or 0-10V
option with BMS input or 0-10V remote control input.
All units are available in 2 or 4 pipe options, and all units
are supplied with pre-fitted valves.
VSI models
can be mounted vertically (recessed wall
mounting) or horizontally (recessed ceiling mounted), with
the option for remote mounted control or 0-10V option
with BMS input or 0-10V remote control input.
1.4 Technical data
2 PIPES
Technical Data (DC)
Model VS
VS 7-2P
VS 9-2P
VS 11-2P
VS 13-2P
VS 15-2P
Model VSI
VSI 7-2P
VSI 9-2P
VSI 11-2P
VSI 13-2P
VSI 15-2P
Length VS
mm (inch)
735 (29)
935 (37)
1135 (45)
1335 (53)
1535 (61)
Length VSI
mm (inch)
378 (15)
578 (23)
778 (31)
978 (39)
1178 (46)
Heat exchanger water content VS/VSI
L (US Gal)
0.47 (0.12)
0.8 (0.21)
1.13 (0.30)
1.46 (0.39)
1.8 (0.48)
Maximum working pressure
bar (psi)
10 (145)
10 (145)
10 (145)
10 (145)
10 (145)
Maximum inlet water temperature
°C (°F)
82 (180)
82 (180)
82 (180)
82 (180)
82 (180)
Minimum inlet water temperature
°C (°F)
4 (39)
4 (39)
4 (39)
4 (39)
4 (39)
Water connections
Eurocone 3/4" Eurocone 3/4" Eurocone 3/4" Eurocone 3/4" Eurocone 3/4"
Power supply
V/ph/Hz
115/1/60
115/1/60
115/1/60
115/1/60
115/1/60
Maximum current
A
0.22
0.32
0.36
0.52
0.56
Maximum power
W
11
19
20
29
33
Weight VS
kg (lbs)
17 (38)
20 (44)
23 (51)
26 (58)
29 (64)
Weight VSI
kg (lbs)
9 (20)
12 (27)
15 (33)
18 (40)
21 (47)
IP units are converted from SI equivalent – all IP units nominal