37
iVector S2
Installation manual
iVector S2 • 2022-07-01
US
8.14 Room temperature probe regulation offset
As the detection probe is towards the bottom of the
device, the temperature detected may at times differ
from the actual room temperature.
By using this function, the value displayed can be
adjusted in a range from -9/+12 K (16 °F - 54 °F) in
intervals of 0.1°C/°F.
Use this adjustment with care, and only after having
confirmed a discrepancy compared with the actual
room temperature using a reliable device.
Key
Operation
Display
With the display off, press and hold the - key for 5 seconds to
access the menu which allows adjustment (using the + and -
keys) of the AIR probe offset displayed, from -9 to +12 K (16 °F
- 54 °F) in 0.1 K/°F intervals.
After 20 seconds from the last action, the panel switches off
and the setting is stored.
8.15 Switching off for longer periods
The antifreeze function is not active if the
electrical supply to the unit is isolated.
Care must be taken to prevent damage from
freezing if the unit is switched off for a season or
for holidays.