Pre-Energization Checks
4
9
Control Panel Wiring Pull Test Locations
Finally, switch the Control Panel Mode Selector into
Repair Service Mode.
Rotate the Mode Selector counter clock-wise (CCW) until the RED handle points to
OFF.
While in Repair Service Mode, the Protection Relay cannot CLOSE the MV breakers,
only TRIP commands or TRIP-on-fault actions will operate.
Reference the image number callouts for additional verification
locations:
1. Perform a gentle control wiring pull test of the AC control power terminations
2. Perform a gentle control wiring pull test of the PT, CT, and VFI Breaker position
terminations
Mode Selector Switch Shown in ON / Automatic Position