Initial Energization
57
Fused PT References Shown OPEN, for Voltage Testing
With all three (3) fused PT references closed, the following verifications may be made
using the SEL-735 Meter and SEL-751 Protection Relay:
L-L interconnection voltages
If L-L (or L-N) voltages are not within the expected interconnection ranges,
verify the PTR and CTR settings in the SEL-735 Meter and SEL-751 Protection
Relay
Frequency
Phase Rotation
For information regarding operation of the SEL-735 or SEL-751 for the purposes of the
verifications above, please reference to the SEL Instruction Manuals ay
https://www.selinc.com, or give us a call.
Please continue to the next section, Operational Testing, for relay operation (CLOSEing-
In)