Pre-Energization Checks
43
MV Termination Verification
On both the Utility Side and Solar Side, all six (6) MV elbows should be be fully seated
on the inserts.
200A load-break connections are pushed on until the are fully seated and no “color ring”
is visible.
600A dead-break connections (e.g. “T-bodies”) are bolted on and need to be fully
seated and torqued per manufacturer instructions.