Pre-Energization Checks
42
Commissioning Staff Should Have the Following Tools:
Ground Resistance Tester
Multimeter w/ resistance (Ω) testing
Grounding Verification
It is important that the myPV ClearSky be properly grounded to prevent any transient
voltages from not having a safe path to ground.
Due to the myPV ClearSky’s location on an equipment pad and grounding ring, Solar-
Ops recommends the maximum ohmic resistance between the device grounding rod
and the associated ground will be < 2Ω.
Both the Utility Side and Solar Side grounds should be verified.