MP SERIES™ Battery Backup System
for Traffic Signals: MP2000E System
Volume One: Operating Manual
Page 6-50
Figure 6-32: Parameter Change Screen
Details on using the menu screen are presented in Section 6.c.5.
SETPOINT
DESCRIPTION/REMARKS
DEFAULT
SETTINGS
SETTINGS
RANGE
Number
Name
40
Hi Lmt
On Battery Mode Line / Buck to
Battery:
Detect Hi Lmt and transfer to
BATTERY mode (when enabled) or
LINE mode when line voltage exceeds
setting.
Buck Off
130 VAC
Buck On
150 VAC
120~150
VAC
46
Buck Hi Line to Buck:
Activate BUCK Mode (when enabled)
when line voltage exceeds setting,
reducing the output.
130 VAC
120~144
VAC
42
Hi Hyst Battery to Line:
Detect Hi Hyst when input voltage
returns below this level; transfers
back to LINE mode from BATTERY
mode.
Buck Off
125 VAC
Buck On
145 VAC
Auto
Auto
47
Buck Lo Buck to Line:
Detect Buck Low when input voltage
returns below this level; releases the
BUCK mode (when enabled) and
transfers back to LINE mode.
125 VAC
Auto
Normal
-
120 VAC
44
Boost Hi Boost to Line:
Detect Boost High when input voltage
returns above this level; releases the
BOOST mode (when enabled) and
transfers back to the LINE mode.
107 VAC
Auto
45
Boost
Lo
Line to Boost:
Detect Boost Low when input voltage
is reduced below this level; transfers
unit to BOOST mode (when enabled)
increasing the output.
102 VAC
96~120 VAC
43
Ly Hyst Battery to Line:
Boost Off
105 VAC
Auto
Auto
SLOW DETECT HIGH LIMIT [130]
Enter new value. (120-150)
>_
Name of
Parameter
Prompt
Current Parameter
Status
Acceptable
Parameter Limits