MP SERIES™ Battery Backup System
for Traffic Signals: MP2000E System
Volume One: Operating Manual
Page 6-94
6.c.6.12.1 Making the IPV4 Ethernet-to-Serial Connection
Use either the Etm.exe utility or make a RJ45 cross-over cable direct connection
between
a PC and the MP2000E Ethernet-to-serial adapter.
An RJ45 cross-over cable direct connection requires administrator’s access to the PC.
6.c.6.12.1.1 Using a Direct PC to Ethernet Card Connection
Interconnect the MP2000E Ethernet card and PC with an RJ45 cross-over cable.
Go to the PC’s Networks Settings and select
“ Internet Protocol (TCP/IP)” then “Properties.”
With the Ethernet-to-serial adapter card set to default IP 192.168.0.10
set the PC to a fixed IP address of 192.168.0.xxx,
where xxx is any number zero to 255 except 10.
Leave the subnet mask at 255.255.255.0. These steps are illustrated in Figure 6-86.
Figure 6-86: Using a Direct PC to Ethernet Card Connection
Performing these tasks requires Administrator’s access to the PC.