A Murrelektronik Company
A Murrelektronik Company
43
Value
85 (0x55h)
Name
Data Type
Byte
Bits
Description
Command
Byte
1
Command for index pointer (which message you’re sending)
Port 2B Kp
2
Output 2B proportional set point (0-250 = 0-2.50, >250=0) default 100
Port 2B Ki
3
Output 2B integral set point (0-250 = 0-2.50, >250=0) default 100
Port 3A Kp
4
Output 3A proportional set point (0-250 = 0-2.50, >250=0) default 100
Port 3A Ki
5
Output 3A integral set point (0-250 = 0-2.50, >250=0) default 100
Port 3B Kp
6
Output 3B proportional set point (0-250 = 0-2.50, >250=0) default 100
Port 3B Ki
7
Output 3B integral set point (0-250 = 0-2.50, >250=0) default 100
Not used
8
J1939 Output Configuration 4
Value
86 (0x56h)
Name
Data Type
Byte
Bits
Description
Command
Byte
1
Command for index pointer (which message you’re sending)
Port 4A Kp
2
Output 4A proportional set point (0-250 = 0-2.50, >250=0) default 100
Port 4A Ki
3
Output 4A integral set point (0-250 = 0-2.50, >250=0) default 100
Port 4B Kp
4
Output 4B proportional set point (0-250 = 0-2.50, >250=0) default 100
Port 4B Ki
5
Output 4B integral set point (0-250 = 0-2.50, >250=0) default 100
Not used
6
Not used
7
Not used
8
J1939 Output Configuration 5