42
Value
84 (0x54h)
Name
Data Type
Byte
Bits
Description
Command
Byte
1
Command for index pointer (which message you’re sending)
INMODE8A
4 bit
2
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x7=Digital Positive
Frequency, 0x8= Counter
INMODE8B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20ma (4000-
20000), 0x4= 0-5V DC (0-5000), 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
Port 1A Kp
Byte
3
Output 1A proportional set point (0-250 = 0-2.50, >250=0) default 100
Port 1A Ki
4
Output 1A integral set point (0-250 = 0-2.50, >250=0) default 100
Port 1B Kp
5
Output 1B proportional set point (0-250 = 0-2.50, >250=0) default 100
Port 1B Ki
6
Output 1B integral set point (0-250 = 0-2.50, >250=0) default 100
Port 2A Kp
7
Output 2A proportional set point (0-250 = 0-2.50, >250=0) default 100
Port 2A Ki
8
Output 2A integral set point (0-250 = 0-2.50, >250=0) default 100
J1939 Output Configuration 3
Name
Data Type
Byte
Bits
Description
Command
Byte
1
Command for index pointer (which message you’re sending)
OUTMODE1A
4 bit
2
1,2,3,4
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 = 0-100.0%),
0x4=Amps(0-4000 = 0-4.000A)
OUTMODE1B
5,6,7,8
OUTMODE2A
3
1,2,3,4
OUTMODE2B
5,6,7,8
OUTMODE3A
4
1,2,3,4
OUTMODE3B
5,6,7,8
OUTMODE4A
5
1,2,3,4
OUTMODE4B
5,6,7,8
INMODE5A
6
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground
INMODE5B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20ma (4000-20000),
0x4= 0-5V DC (0-5000), 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
INMODE6A
7
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground
INMODE6B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20ma (4000-20000),
0x4= 0-5V DC (0-5000), 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
INMODE7A
8
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x7=Digital Positive Frequency,
0x8= Counter, 0xA=Encoder
INMODE7B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20ma (4000-20000),
0x4= 0-5V DC (0-5000), 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
J1939 Output Configuration 2
Value
83 (0x53h)
***Encoder mode, both 7A and 8A are used for the encoder input. When changing 7A to encoder it automatically sets up 8A to work with it.