5.3.3 CONFIGURING INPUTS
Input Mode
Inputs can be configured in 2 ways, globally, or individually. Both configurations types use the same PGN. PGN 61408 is used for
multiple messages by use of a different value put into the “Command” byte of the PGN. This value is used as an index or pointer as to
where the information goes in the module.
A. Global Input Configuration
(Only used if you want all the inputs to be configured the same. Only works for digital configuration.)
Configuring all of the inputs is done through the “MODE2” byte in PGN 61408. The J1939 message structure,
Name
Data Type
Byte
Bits
Description
Command
Byte
1
Command for index pointer (which message you’re sending)
Ctrl Mode Reset
2 bit
2
1,2
Enables Controller Mode Output Reset
Enable Status 1 Msg
3,4
Enables the constant transmission of status message 1
Enable Status 2 Msg
5,6
Enables the constant transmission of status message 2
Enable Amp Msg
7,8
Enables the constant transmission of amperage messages
Enable 24V DC
3
1,2
Enables the low and over voltage fault limits for 24V DC system
Save Configuration
3,4
Saves the configuration to the module (otherwise changes only valid until a power cycle occurs),
set to 1 to write configuration to module
Analog raw value
5,6
Internal Use Only
7,8
4
1,2
3,4
5,6
7,8
FREQ1
Word
5
Sets the global configuration of the frequency for all channels.
Low Byte FREQ1: Value in decimal (40 - 1100 Hz). Example: 0xC8h = 200d = 200 Hz.
6
High Byte FREQ1
MODE1
4 Bit
7
Sets the configuration of ALL the outputs, overides Command 53 and 54. (0=Mode 1 Not Used, 1=ON/
OFF, 2=Data 0-4000, 3= Percent 0-100.0%(0-1000),
4= Amps (0-4000ma) Can't be used in this mode
MODE2
4 Bit
7
Sets the configuration of the inputs.(0=Mode 2 Not Used, 1=Digital Positive, 2=Digital Ground)
No analog
ID1
Byte
8
User defined byte for configuration ID, this will be transimitted in the STAT message.
PGN
61408 (0xEFE0) Node offset of 0
Source Address
(0x?? (CSA*))
PDU Format
239 (0xEF)
PDU Specific
224 (0xE0)
Built Message
(0x18EFE0??)
Transmit rate
50 ms
Msg timeout
200 ms
Priority
6
DP
0
Command Value
82 (0x52)
*CSA - Controller Source Address