Operation of the System
SUPREMATouch
39
US
Normally energised/Normally de-energised
Field type: Selection
Set the operating mode for the selected relay output:
-
Normally energised [closed circuit]:
The relay coil is energised in the no alarm status and is de-energised in the alarm status.
The output delivers in the set-condition [Alarm, Failure] a LOW-Signal, this is called a connect-
ed relay is not energised. [The Normally energised principle]
-
Normally de-energised [open circuit]:
The relay coil is de-energised in the no alarm status and is energised in the alarm status.
The output delivers in the set-condition [Alarm, Failure] a HIGH-Signal, this is called a connect-
ed relay is energised. [The Normally de-energised principle]
Tag
Field type: text
Enter a customer specific designation for the selected relay output.
Blk. [flashing]:
Element type: Checkbox
If this field is set, the relay flashes at a frequency of approx. 1 Hz when activated. This function
doesn't work together with the inhibit condition.
New Alarm [i. e. actual alarm]
Field type: Check boxes
If this field is set, the relay output selected can be set to “normal” status by pressing the <ACKNL>
key even if the signal value has been outside the alarm threshold limits.
Al. 1-4 [1st-4th Alarm]
Field type: Check box
In this field, select the alarms that will cause the selected relay output to be activated, for the input
shown in the “channel” column in the specific line.
Fail
Field type: Check box
If this condition is set, the selected relay output is activated when an error [fault] occurs for the
input shown in the “channel” column in the specific line.
Inhibit
Field type: Check box
If this condition is set, the selected relay output is activated when the input shown in the “channel”
column in the specific line is inhibited.
Содержание SUPREMA Touch
Страница 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Страница 7: ...SUPREMATouch 6 Contents MSA US...
Страница 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Страница 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Страница 304: ...MSA AUER MSA Dimensions SUPREMA 303 GB 16 2 Rail mounted Modules MRO 8 TS Module MRO 16 TS Module...
Страница 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Страница 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Страница 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...