Operation of the System
SUPREMATouch
19
US
LED Indicators and Alarms
The 8 LED indicators provide system and signal status information.
SYSTEM:
SIGNAL:
Alarms can be latching or non-latching [also see Measure Points].
Non-latching alarms:
When a signal exceeds the alarm threshold a new alarm is triggered and the corresponding LED
flashes at a frequency of 0.5 Hz. Pressing the ACKNL [acknowledge] key makes the LED change
to ‘steady state’. When the signal is below the alarm threshold, the LED will turn off, regardless of
whether the alarm has been acknowledged or not. For non-latching alarms, the RESET key has
no effect.
Latching alarms:
When a signal exceeds the alarm threshold a new alarm is triggered and the corresponding LED
flashes at a frequency of 0.5 Hz. Pressing the ACKNL [acknowledge] key makes the LED change
to ‘steady state’. When the signal is no longer exceeding the alarm threshold, the LED remains
in ‘steady state’ if the alarm has been acknowledged, or in the ‘flashing state’ if the alarm has not
been acknowledged. If the signal is no longer exceeding the alarm threshold and the alarm has
been acknowledged, the LED is extinguished by pressing the RESET key. If the signal still ex-
ceeds the alarm threshold, pressing RESET has no effect.
Signals that are above full-scale range or signal failures that were caused by an interruption of the
digital communication are always latched. Signals below the measurement range are non-latch-
ing. Measurement values that are over the full-scale range will trigger all 4 alarms.
If an audible alarm device is connected to the horn relay, it will sound as soon as a new alarm is
triggered. It continues to sound even when the alarm condition no longer exists. Pressing the
ACKNL key silences the horn, regardless of whether or not the alarm condition still exists.
-
POWER
[green]
power supply on/off
-
FAIL
[yellow]
system specific error [e.g. defective CPU]
-
INHIBIT
[yellow]
on:
inputs are inhibited or a calibration is pending
blinking: outputs connected to one or more inputs are locked
-
AL 1–AL 4
[red] input signal alarms
[each input can have up to four alarms]
-
FAIL
[yellow]
specific input signal statuses
[measurement values that are over full-scale, below the measure-
ment range and signal failures]
When a redundant system is used, the RESET or ACKNL key has to be pressed for at
least 1 second.
Содержание SUPREMA Touch
Страница 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Страница 7: ...SUPREMATouch 6 Contents MSA US...
Страница 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Страница 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Страница 304: ...MSA AUER MSA Dimensions SUPREMA 303 GB 16 2 Rail mounted Modules MRO 8 TS Module MRO 16 TS Module...
Страница 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Страница 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Страница 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...