SUPREMATouch
120
Description of the System
MSA
US
Display Connection/MDC Module
The Display Connection Unit (MDC module) is used to connect the MDO module to the system.
It's only functions are the physical connection and the selection of the power supply.
D Analog Output: MGO/MRC TS/MRO/MRO TS/MAO Modules
MGO Module (General Output Unit)
The MGO module is provided to display alarm messages or other control signals. It receives the
switching data for the relay output drivers from the MCP module via the CAN bus. The output is
protected against short-circuits and overloads. Driver outputs 1–8 of the first MGO module present
in the system are used to control the 8 common alarms (Alarms 1–4, horn, signal failure, inhibit,
power).
In redundant versions of the system, each of the two MGO modules controls 8 relays on the
MRO 16 TS module (16 common alarm relays/redundant), the working contacts of these relays
are connected in series.
MRC TS Module (Relay Connection) / MRO TS Module (Relay Output)
The output signals of the MGO module are sent over a 40-way ribbon cable from the MUT module
to the MRC TS module and from there over 20-way ribbon cables to the MRO TS relay modules.
•
MGO Module
GENERAL OUTPUT UNIT
(40 switching outputs, 24 V/0.5 A)
•
MRO 10-8 Module
RELAY OUTPUT UNIT
(rack relay module, 8 relays, 230 VAC/3 A contacts)
•
MRC TS Module
RELAY CONNECTION Module
(5 x MRO, 2 x 40 channels, ribbon cable)
•
MRO 10-8 TS Module
RELAY OUTPUT Module
(rail-mount relay module, 8 relays, 230 VAC/3 A contacts)
•
MRO 10-16 TS Module
RELAY OUTPUT Module
(rail-mount relay module, redundant, 16 relays, 230 VAC/3 A
•
MAO Module
ANALOG OUTPUT Module
(source 0 ... 20 mA/500 Ohms load/electrically isolated from sys-
tem power supply)
•
MRO 20-8-TS
RELAY OUTPUT Module
(rail-mount relay module, 8 relays, 230VAC/5A contacts)
•
MRO 20-16-TS
RELAY OUTPUT Module
(rail-mount relay module, 16 relays, 230VAC/5A contacts)
•
MRO 10-16-TS-SSR
SOLID STATE RELAY OUTPUT Module
(rail-mount solid state relay module, 16 relays, 24 VAC/100 mA)
•
MRO20-8-TS SSR
SOLID STATE RELAY OUTPUT Module
(rail-mount solid state relay module, 8 relays, 24 VAC/100 mA)
•
40 relay driver outputs for relays, contactors, magnetic valves, lamps, or LEDs (24 V/0.3 A).
•
The data is transmitted via the CAN bus from the MCP module.
•
The System Failure Relay is activated when a system error occurs.
•
Euro card with a 96-way connector.
Содержание SUPREMA Touch
Страница 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Страница 7: ...SUPREMATouch 6 Contents MSA US...
Страница 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Страница 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Страница 304: ...MSA AUER MSA Dimensions SUPREMA 303 GB 16 2 Rail mounted Modules MRO 8 TS Module MRO 16 TS Module...
Страница 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Страница 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Страница 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...