Connection advice:
Fig. 113 LWL converter connection scheme
The terminator at rack 1 must be de-activated, and a 120 ohms resistor has additionally to be
clamped under the terminal (2 to 4) NET 0 of the CAN connection.
For Net 1 a 120 ohms resistor has additionally to be clamped under the terminal (2 to 4) NET 1 of
the CAN connection. The terminators of both LWL converters must be activated (S5) as well as
the satellite terminator.
SUPREMA CAN LWL Converter
The voltage supply (24 V) of the CAN LWL converter is effected via a COMBICON connector,
which is also equipped with a relay contact for failure output. The CAN bus is equally connected
via a 4-pin COMBICON connector. The LW line is connected via an ST connector. The baudrate
of the converter can be set by means of DIP switches. Additionally, there is an extra switch for the
CAN terminator in the converter.
The LWL converters dispose of a very good diagnosis function which enables them to locate er-
rors very quickly. A bar graph displays the signal quality at the optical fibre side, and a LED indi-
cates possible errors at the „copper“ side.
To guarantee the function of the SUPREMA LWL converters, some points must be taken into con-
sideration in the rup-up. These are:
Fig. 114 LWL converter connector allocation
a)
The CAN baudrate must match with that of the SUPREMA (or CAN bridge).
b)
The line length must align with the baudrate (max. 2000 m).
c)
Take notice of optical fibre line crossing between TD and RD.
Base station
Rack 1
Satellite
Rack 2
Jack
LWL cable
Plug
CAN Line
NET 1
NET 0
CAN Bridge
CBM
LWL Converter
LWL Converter
Содержание SUPREMA Touch
Страница 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Страница 7: ...SUPREMATouch 6 Contents MSA US...
Страница 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Страница 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Страница 304: ...MSA AUER MSA Dimensions SUPREMA 303 GB 16 2 Rail mounted Modules MRO 8 TS Module MRO 16 TS Module...
Страница 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Страница 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Страница 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...