MSA AUER
MSA
Installation
SUPREMATouch
131
US
The maximum length for 40-way ribbon cables is 5 meters.
MUT Module connected to MAT TS Module
Passive/active sensor cables and analog output cables are usually screened. The cable screen is
to be connected directly, over the shortest possible distance, to the screening terminal provided.
MUT Module connected to MRC TS Module
The ribbon cable is to be screened. The cable screen is to be connected directly, over the shortest
possible distance, to the screening terminal provided.
MRC TS Module connected to MRO 16 (8) TS Module
Screened cables are not required to connect the individual relay modules.
Fig. 60
SUPREMA shielding and grounding concept
Содержание SUPREMA Touch
Страница 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Страница 7: ...SUPREMATouch 6 Contents MSA US...
Страница 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Страница 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Страница 304: ...MSA AUER MSA Dimensions SUPREMA 303 GB 16 2 Rail mounted Modules MRO 8 TS Module MRO 16 TS Module...
Страница 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Страница 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Страница 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...