7 Functions and settings
Maschinenfabrik Reinhausen 2014
95
222/08 EN
TAPCON® 240
Volts (V)
Kilovolts (kV)
This value relates to the secondary
voltage of the system's voltage
transformer.
This value relates to the primary
voltage of the system's voltage
transformer.
Table 18: Units available
If you want to change the display from
V
to
kV
, you have to set the trans-
former data of the device to be monitored.
To set the undervoltage limit value of the voltage regulator to be monitored,
proceed as follows:
1.
>
Parameter >
Cross-monitoring > Press
until the de-
sired parameter is displayed.
ð
V< regulator 2.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The undervoltage limit value is set as an absolute value.
Setting relative value
To set the undervoltage limit value of the voltage regulator to be monitored,
proceed as follows:
1.
>
Parameter >
Cross-monitoring > Press
until the de-
sired parameter is displayed.
ð
V< regulator 2.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The undervoltage limit value is set as a relative value.
Setting overvoltage limit value V> for regulator 2
You can use this parameter to set the overvoltage limit value V> of the de-
vice to be monitored. You can set the undervoltage limit value V< as an ab-
solute value (
V
or
kV
).
Setting absolute value
You can use the
key to change the display to the following units:
7.7.3