7 Functions and settings
Maschinenfabrik Reinhausen 2014
115
222/08 EN
TAPCON® 240
Assigning maximum physical parameter
In this display you can assign a maximum physical parameter to the measur-
ing transducer output.
To assign the upper physical parameter to the measuring transducer, pro-
ceed as follows:
1.
Press
>
Configuration >
Continue >
Continue >
Measuring transducer 1 / 2 >
until the desired parameter is dis-
played.
ð
Output 1 top.
2.
Press
or
until the desired physical parameter is displayed.
3.
Press
.
ð
The desired physical parameter is assigned.
Assigning minimum absolute value
In this display you can assign a minimum limit value to the measuring trans-
ducer output as an absolute value.
To assign the minimum absolute value, proceed as follows:
1.
>
Configuration >
Continue >
Continue >
Meas-
uring transducer 1 / 2 > Press
until the desired parameter is dis-
played.
ð
Output 1 lower value.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The minimum absolute value is assigned.
Assigning maximum absolute value
In this display you can assign a maximum limit value to the measuring trans-
ducer output as an absolute value.
To assign the maximum absolute value, proceed as follows:
1.
>
Configuration >
Continue >
Continue >
Meas-
uring transducer 1 / 2 > Press
until the desired parameter is dis-
played.
ð
Output 1 upper value.
2.
Press
to increase the value or
to reduce it.
7.12.3
7.12.4
7.12.5