![MR tapcon 240 Скачать руководство пользователя страница 149](http://html.mh-extra.com/html/mr/tapcon-240/tapcon-240_operating-instructions-manual_1844358149.webp)
9 Fault elimination
Maschinenfabrik Reinhausen 2014
149
222/08 EN
TAPCON® 240
Characteristics/detail
Cause
Remedy
Step display incorrect.
▪
Display fluctuates.
Interference.
Shield the line.
Increase distance from source of interfer-
ence.
Lay interference lines separately.
Route signal in separate lines (filter,
shielded lines).
No step display.
▪
"-" is displayed.
No measurement signal.
No L- for digital input.
Connect signal as shown in connection di-
agram.
Check wiring.
Review status screen.
Connect as shown in connection diagram.
No step display.
▪
"?" is displayed.
Bit combination (code) im-
permissible.
Check wiring.
Review status screen.
"Motor running" signal pres-
ent.
Check signal sequence
Review status screen.
Table 41: Tap position capture
Other faults
If you cannot resolve a problem, please contact Maschinenfabrik Reinhau-
sen. Please have the following data to hand:
▪
Serial number
This can be found:
▪
Outer right side when viewed from the front
▪
Info screen (
>
Info)
Please provide answers to the following questions:
▪
Has a firmware update been carried out?
▪
Has there previously been a problem with this device?
▪
Have you previously contacted Maschinenfabrik Reinhausen about this
issue? If yes, then who was the contact?
9.7