7 Functions and settings
Maschinenfabrik Reinhausen 2014
114
222/08 EN
TAPCON® 240
▪
V2 (optional via a second measurement input)
▪
I1
▪
Active current
▪
Reactive current
▪
Active power
▪
Reactive power
▪
Apparent power
▪
Tap position
▪
Desired value
If the analog outputs have not been set as you want them in the factory, the
section below describes how you can adjust the measuring transducer.
Linking measured value with output
In this display you can assign a measured value to be transferred to the
measuring transducer output.
In order to assign a measured value to the measuring transducer output,
proceed as follows (example using measuring transducer 1/2; "output 1
measured value"):
1.
>
Configuration >
Continue >
Continue >
Meas-
uring transducer 1/2.
ð
Output 1 measured value.
2.
Press
or
until the desired option is displayed.
3.
Press
.
ð
The desired measured value is assigned.
Assigning minimum physical parameter
In this display you can assign a minimum physical parameter to the measur-
ing transducer output.
To assign the lower physical parameter to the measuring transducer, pro-
ceed as follows:
1.
Press
>
Configuration >
Continue >
Continue >
Measuring transducer 1 / 2 >
until the desired parameter is dis-
played.
ð
Output 1 bottom.
2.
Press
or
until the desired physical parameter is displayed.
3.
Press
.
ð
The desired physical parameter is assigned.
7.12.1
7.12.2