7 Functions and settings
Maschinenfabrik Reinhausen 2014
100
222/08 EN
TAPCON® 240
Setting parameter
Current feed
Display
Primary current
Secondary cur-
rent
Power connection
Info screen
Primary/secon-
dary current
Main screen
No parameteriza-
tion
Unknown
1 A
100 %
0 A
No parameteriza-
tion
1 A
1 A
1 A
0 A
50 A
Unknown
1 A
100 % (of primary
current)
50 A (of primary
current)
50 A
1 A
1 A
1 A (of secondary
current)
50 A (of primary
current)
Table 21: Example of unit displayed: %/A
To set the primary transformer current, proceed as follows:
1.
>
Configuration >
Transformer data > Press
until the
desired parameter is displayed.
ð
Primary current.
2.
Press
to highlight the position.
ð
The desired position is highlighted and the value can be changed.
3.
Press
to increase the value or
to reduce it.
4.
Press
.
ð
The primary transformer current is set.
Setting the current transformer connection
This parameter can be used to set the current transformer connection. This
setting is needed for the device to display the correct secondary current in
the info screen.
If you select the "Unknown" option, the percentage of current (with reference
to the current transformer connection used) is displayed in the info screen.
▪
0.2 A
▪
1 A
▪
5 A
To set the current transformer connection, proceed as follows:
7.8.4