7 Functions and settings
Maschinenfabrik Reinhausen 2014
69
222/08 EN
TAPCON® 240
Figure 42: Recommended bandwidth
U
n-1
Step voltage of tap position n-1
U
n
Step voltage of tap position n
U
nom
Nominal voltage
The following transformer values are used to determine the recommended
bandwidth:
Nominal voltage U
nom
= 11,000 V
Step voltage in tap position 4 U
Step4
= 11,275 V
Step voltage in tap position 5 U
Step5
= 11,000 V
The following section describes how you can set the bandwidth.
Setting the bandwidth
To enter the determined bandwidth, proceed as follows:
1.
>
Parameter >
Control parameter > Press
until the
desired parameter is displayed.
2.
Press
to highlight the position.
ð
The desired position is highlighted and the value can be changed.
3.
Press
to increase the value or
to reduce it.
4.
Press
.
ð
The bandwidth is set.
7.4.2.2