7 Functions and settings
Maschinenfabrik Reinhausen 2014
129
222/08 EN
TAPCON® 240
1.
>
Configuration >
Continue >
Continue >
Comm. interface 1.
ð
Comm. connection CIC1.
2.
Press
or
to set the option you want.
3.
Press
.
ð
The communication port is selected.
Selecting communication baud rate
You can use this parameter to set the desired baud rate for the communica-
tion interface. You can select the following options:
▪
9.6 kilobaud
▪
19.2 kilobaud
▪
38.4 kilobaud
▪
57.6 kilobaud
The baud rate of 57.6 kilobaud is only active for communication interfaces
RS232, RS485 and fiber-optic cable.
A baud rate of 57.6 kilobaud cannot be used for Ethernet.
This display is only provided for the following interface protocols:
▪
DNP3
▪
IEC 60870-5-101
▪
IEC 60870-5-103
▪
MODBUS ASCII/RTU
▪
ABB SPA
To set the communication interface baud rate, proceed as follows:
1.
Press
>
Configuration >
Continue >
Continue >
Comm. interface Press >
until the desired parameter is displayed.
ð
Baud rate comm. CIC1.
2.
Press
or
to set the option you want.
3.
Press
.
ð
The baud rate is selected.
Assigning network address
You can use this parameter to assign a network address (IPv4) to the de-
vice. If you want to connect the device by means of Ethernet, you need to
set a valid network address.
7.14.2
7.14.3