7 Functions and settings
Maschinenfabrik Reinhausen 2014
104
222/08 EN
TAPCON® 240
Circuit F
TAPCON® 240
Figure 64: Phase difference -30 3PH
▪
The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪
The current transformer CT is looped into the outer conductor L1.
▪
The current I
L1
lags behind U
L1
-U
L2
by 30°. This corresponds to a phase
shift of -30°.
▪
The voltage drop on an outer conductor is determined by the current I
L1
.
To set the phase difference for the transformer circuit, proceed as follows:
1.
>
Configuration >
Transformer data > Press
until the
desired parameter is displayed.
ð
Transformer circuit.
2.
Press
or
to select the required phase difference.
3.
Press
.
ð
The phase difference is set.
Parallel operation
In the
Parallel operation
menu item, you can set the parameters needed for
parallel transformer operation. Parallel transformer operation is used to in-
crease the throughput capacity or short-circuit capacity in one place.
Compliance with the following general conditions is required for operating
transformers in parallel:
▪
Identical rated voltages
▪
Transformer power ratio (< 3 : 1)
▪
Maximum deviation of short-circuit voltages (U
K
) for transformers con-
nected in parallel < 10%
▪
Same number of switching groups
▪
The same current-transformer connection has to be used for all devices
running in parallel
7.9
Conditions for parallel
operation