F02
Range
Default
F02.017
Jog Speed:
Speed setpoint in Volt for Jog operations by use of input
“Jog forward” or “Jog reverse”.
0.01 … 10.00
1.00
F02.018
Jog / Homing Ramp:
Ramp time in seconds for Jog operations and homing
sequence with respect to speed changes between
standstill and maximum speed (setpoint 10 V)
0 … 99
1
F02.019
Home Speed High:
Fast Homing speed setpoint in Volts. Every homing cycle
will start with this speed.
0.01 … 10.00
2.00
F02.020
Home Speed Low:
Slow Homing speed setpoint in Volt. A Homing cycle
will end with this speed.
0.01 … 10.00
0.50
F02.021
Home Switchpoint:
Distance from the final home position where the speed
changes over from high speed to low speed within a
homing cycle.
Setting scaled in length units.
1 … 99999
100
F02.022
+/- Sync. Rate (%):
This register allows a percental adaption of the
synchronous speed in a range of +/- 99.99%. In general,
this register will be set to 0 and the cutting roll will
synchronize with the line exactly according to the
encoder information.
Some applications may require slightly higher or lower
speed during the synchronous zone, e. g. due to the
cutting tool design.
This setting affects the synchronous speed only, but not
the cutting length!
-99.99
…+99.99
0
F02.023
Alarm Level:
Defines the switching threshold of the output “Alert”
when the system is forced out of synchronization due to
external events (drive fault or mechanical problem).
Setting occurs in cutting roll encoder increments and
the Alert output switches on when the positional error
of the roll in respect to the scheduled position
overpasses the number of encoder pulses set.
0 … 9999
100