SPB: SPC is Offline (148)
Safety processor B reports safety processor C is not communicating. The
car will perform an emergency stop and will not be allowed to move. All
calls will be canceled and the doors will not be allowed to move. May
occur subsequent to an unsuccessful parameter update. Cannot be
bypassed.
System Verifies:
- SPC sequence numbers offline
Correction:
1. Press SCE-CPU board RSTC button.
2. If the processor resets, monitor activity for recurrence.
SPB: UETS Position High (401)
Traction only. SPB reports the car encountered the Up Emergency Termi-
nal Switch at a position higher than the position learned during the learn
operation.
Correction:
1. Verify position of switch (software or physical).
2. Relearn limit switches (Utils > Landing System Utilities > Terminal
Switch Learn).
SPB: UETS Position Low (400)
Traction only. SPB reports the car encountered the Up Emergency Termi-
nal Switch at a position lower than the position learned during the learn
operation.
Correction:
1. Verify position of switch (software or physical).
2. Relearn limit switches (Utils > Landing System Utilities > Terminal
Switch Learn).
SPB: UETS Speed High (390)
Traction only. SPB reports the car was travelling faster than the learned
speed plus the delta upon encountering the Up Emergency Terminal
Speed switch. Car will perform an emergency stop, then proceed at cor-
rection speed to the terminal.
Correction:
1. Verify position of switch (software or physical).
2. Relearn limit switches (Utils > Landing System Utilities > Terminal
Switch Learn).
SPC Started Up (168)
SPC reports it has booted up. Cannot be bypassed.
SPC: 3HN Comm Loss (255)
Safety processor C is reporting that serial hall call communications have
been lost. The system will begin emergency dispatch operation. Cannot
be bypassed.
Correction:
1. Check power to hall call bus (fuse F24HWY on SCE-UPD board).
SPC: CAN Comm Loss (224)
Safety processor C is reporting CAN communications have been lost.
Cannot be bypassed.
SPC: CAN3 Comm Loss (171)
Safety processor C is reporting CAN 3 (Serial Hall Call) communications
have been lost. Cannot be bypassed.
Correction:
1. Check CAN connections for hall call bus (CANH3/CANL3) on SCE-CPU.
SPC: SPA is Offline (226)
Safety processor C reports that Safety Processor A is not communicating.
Car will perform an emergency stop and will not be allowed to move. All
calls will be canceled and doors will not be allowed to move. May occur
subsequent to an unsuccessful parameter update. Cannot be bypassed.
System Verifies:
- SPA sequence numbers offline
Correction:
1. Press SCE-CPU board RSTA button.
2. If the processor resets, monitor activity for recurrence.