Configuration and Troubleshooting
2-56 Manual # 42-02-2P26
Cartop Construction (55)
The car is on construction operation and is being operated from the car-
top inspection station. Cannot be bypassed.
System Verifies:
- Mode of Operation = Construction CT
Correction:
1. Exit construction operation (
Construction Operation on page 1-8
Cartop Insp./Bypass (127)
Cartop inspection is active and one or both of the Car/Hoistway Door
Bypass switches is in the Bypass position. Cannot be bypassed.
System Verifies:
- ModeofOperation = OpModeInspectionBPCT
Correction:
1. Turn off one or both of the Car/Hoistway Door Bypass switches.
Cartop Inspection (59)
The car is on Cartop Inspection mode. Cannot be bypassed.
System Verifies:
- Mode of Operation = Inspection CT
Correction:
1. If in error, verify cartop inspection inputs. 24VDC at INCT disables car
top inspection.
CDB Switch Fault (328)
Generated when the CDB and CDBO inputs are in the same state indicat-
ing a possible failure of the car door bypass switch.
Correction:
1. Toggle the car door bypass switch and verify that the diagnostic LEDs
for the switch also toggle (CDB, CDBO). PLD Inputs, screen 1.
2. Verify that the CDBTST jumper is inserted in the OFF position.
Cell Battery Volts Low (374)
Low SCE-CPU battery voltage. Battery backs-up run time parameters.
Informational. Replace battery.
CFG Err: 2-Stop Config (268)
Generated when a car is set to be a two stop installation and the CONFIG
terminal is low (0V). Alternatively, when the car is set to be more than
two stops and the CONFIG terminal is high (+24V). Also generated if
both the CONFIG terminal and the DLMS terminal are high (+24V).Can-
not be bypassed.
Correction:
1. Verify top and bottom floor settings in the Building Setup menu.
2. Check voltage at the CONFIG terminal matches the settings.
3. Check voltage at the DLMS terminal matches settings.
CFG Err: Car Panel Insp (269)
User defined car panel inspection settings and car panel inspection hard-
ware configuration do not match. Cannot be bypassed.
Correction:
1. Verify touch screen settings against job prints.
2. Verify actual installation against job prints.
CFG Err: Controller Type (267)
The user defined controller type (Traction/Hydraulic) does not match the
hard wired default at SCE-CPU input TR_HY. (TR_HY at ground for trac-
tion applications; TR_HY at 24VDC for hydraulic applications.) Cannot be
bypassed.
Correction:
1. Verify correct controller type on touch screen (CONFIG 01 > Building
Setup > Controller Type).
2. Verify state of SCE-CPU board TR_HY input (IDC, upper right edge of
SCE-CPU board). If not in accordance with description above, contact
MCE.