Troubleshooting Reference
2-79
element
TM
Series
Random Hall Calls Gen (157)
The random hall call generator has been activated. This generator is used
to exercise the elevator using random hall calls.
Correction: Check parameter setting.
Recall Complete (453)
Car has completed recall for the specified mode of operation and is at the
user defined recall floor and has completed the configured door operation
at that floor. Fault-bypassed in Construction/Inspection.
Correction:
1. If in error, verify inputs and programming (Config 01 > Configure
Spare Inputs) for specified recall action.
Recall Done (292) (442)
Car has completed recall operation.
Correction: Check recall input.
Recall Done Switch 1 (116)
Recall Done Switch 2 (117)
Recall Done Switch 3 (118)
Recall Done Switch 4 (119)
The car has completed recall in response to the indicated recall switch
and has completed the configured door operation at the floor. Cannot be
bypassed.
System Verifies:
- Recall Data = Recall Switch ‘n’
- Recall Data = Complete
Correction:
1. If in error, verify inputs and programming (Config 01 > Configure
Spare Inputs) for specified recall action.
Recall Sw: Bypassed (373)
Informational. An active recall switch is bypassed due to a higher mode
of operation.
Recall Switch 1 (41)
Recall Switch 2 (42)
Recall Switch 3 (43)
Recall Switch 4 (44)
Recall switch “n” has been activated. Fault-bypassed in Construction.
System Verifies:
- Mode of operation = Recall Switch ‘n’
- Recall Data Type = Recall Switch ‘n’
- Recall Data, Complete is not True.
Correction:
1. If in error, verify no input is programmed (Config 01 > Configure Spare
Inputs) for this recall switch.
2. Otherwise, verify switch mechanically and electrically.
3. Verify state of input and input wiring.
Recalling (5)
Car is recalling to selected recall floor (fire service, Pretest operation, Aux
power, Recalling switches, Floor operation, or PTI input). Fault-bypassed
in Construction/Inspection.
Correction:
1. If in error, verify that the assigned recall input (System IO > Pro-
grammed Inputs) is inactive.
2. Verify user defined recall floor.
Recalling Switch 1 (112)
Recalling Switch 2 (113)
Recalling Switch 3 (114)
Recalling Switch 4 (115)
The indicated recall switch is active. Hall calls are canceled or reassigned.
Car calls disposition is according to user settings for the switch. Cannot
be bypassed.
Correction:
1. If in error, verify that the input is wired correctly. If not used, verify
that the input is not programmed; (System IO > Programmed Inputs).
SAFH Input Low (163)
The hoistway safety string input is low. Car will perform an emergency
stop or, if at a floor, will not move. Doors remain as they are.
System Verifies:
- SAFH Input is low
- SAFC input high
Correction:
1. If in error verify input and input devices mechanically and electrically.
Table 2.15 Touch Screen Event Listings
Event
Description
Содержание Nidec Element Series