F1: Program Mode
4-45
4
Motion 4000
• HOSPITAL EMERG. OPERATION?
• When selected, enables Hospital Emergency Operation. Typically, a hospital emer-
gency call switch is installed at each floor where this service is desired.
• If you do not have Hospital Emergency Service Operation, set the option to NO by
pressing the S button. Then, press the N push button to exit.
• If you have Hospital Emergency Service Operation, set the option to YES by pressing
the S button, then the
N
button to continue. A landing number display will appear.
• If you want Hospital Emergency Service to this landing, press S to set to Yes. (If you
change your mind, press S a second time to go back to No.)
• Press the '+' push button to scroll through available landings. Press N to continue after
making settings for a floor.
• If this car has rear doors, the sequence will repeat.
• Press the '+' button to scroll through available landings. The display will continue to
present options for each floor. Press N to exit the Hospital Emergency Service option.
• When a hospital emergency call switch is activated, the hospital emergency call registered
light will light at that floor only and the nearest available elevator will respond to the call. All
car calls in the selected car will be canceled and any landing calls which had previously been
assigned to the car will be transferred to another car if available.
• If the selected car is traveling away from the hospital emergency call, it will slow down and
stop at the nearest floor without opening the doors, reverse direction, and proceed nonstop
to the hospital emergency floor.
• If the selected car is traveling toward the hospital emergency floor, it shall proceed nonstop
to that floor.
• If, at the time of selection, the car is slowing into a floor, it will stop without opening the
doors, then travel immediately to the hospital emergency floor.
• When the car reaches the hospital emergency floor, it will remain with doors open for a
timer-determined time. After this interval has expired, if the car has not been placed on in-
car Hospital Emergency Service Operation, the car will return to normal service.
• A hospital emergency key switch in each car operating panel is used to select in-car Hospital
Emergency Service Operation. Upon activation of the key switch, the car will be ready to
accept a call to any floor and, after the doors are closed, will proceed nonstop to that floor.
Returning the key switch to the normal position will restore the car to normal service
.
• The car selected to respond to a hospital emergency call is removed from automatic service
and will accept no additional calls, emergency or otherwise, until it completes the hospital
emergency function. In duplex installations, if both cars are out of service and unable to
answer an emergency call, the hospital emergency call registered light will not illuminate.
• Four outputs on the first HC-UIO board are used for hospital emergency service calls.
Hospital Emergency Operation (HEO) will flash once the car has been selected to respond to
a hospital emergency call and will remain flashing until the in-car hospital switch is
returned to normal or the time interval that the car must wait for the in-car switch to be
turned ON expires.
Hospital Emergency Warning Indicator (HWI) will remain steadily ON for a car on Inde-
pendent Service when the hospital call is registered.
Hospital Emergency Select (HSEL) will remain steadily ON, indicating that the car has been
selected to answer a hospital call, until the in-car hospital switch is turned ON or the time
interval expires.
Hospital Emergency Phase 2 (HOSPH2) will remain ON, indicating that the car has arrived
at the hospital call floor until the in-car hospital switch is returned to normal or the time
interval that the car must wait for the in-car switch to be turned ON expires.
Содержание Motion 4000
Страница 20: ...xiv Manual 42 02 2P24 5 20 13 ...
Страница 38: ...Motion 4000 Traction Elevator Control 1 18 Manual 42 02 2P24 ...
Страница 178: ...Final Adjustments 3 56 Manual 42 02 2P24 ...
Страница 322: ...User Interface 4 144 Manual 42 02 2P24 ...
Страница 391: ...PC Board Quick References 5 69 5 Motion 4000 Figure 5 11 Example MC CPI Wiring ...
Страница 439: ...Customer Notations A 27 A Motion 4000 Customer Notations Table A 4 Customer Notation Area ...
Страница 444: ...Appendix A 32 Manual 42 02 2P24 ...