background image

Operation

ProStar MPPT Operator’s Manual

41

40

4.0

the battery voltage above the standard absorption voltage 

so that the electrolyte gases. The green SOC LED will blink 

rapidly two (2) times per second during equalization charg-

ing. The duration of the equalize charge is determined by 

the selected battery type. See table 4-1 in this section for 

more details. The 

Equalization Time

 is defined as time spent 

at the equalization set-point. If there is insufficient charge 

current to reach the equalization voltage, the EQ will termi-

nate after an additional 60 minutes to avoid over gassing 

or heating of the battery.  If the battery requires more time 

in equalization, with non-metered versions, manual EQ can 

be activated using the push-button (see Section 4.5) to 

continue for one or more additional EQ cycles.  The Prostar 

MPPT meter, or MSView software, can also be used to 

program EQ timing and duration.  
The Equalization set-point is temperature compensated 

through either the on-board local temperature sensor, or an 

optional Remote Temperature Sensor (RTS), if connected.

Why Equalize?

Routine equalization cycles are often vital to the perfor-

mance and life of a battery - particularly in a solar system.  

During battery discharge, sulfuric acid is consumed and 

soft lead sulfate crystals form on the plates.  If the battery 

remains in a partially discharged condition, the soft crystals 

will turn into hard crystals over time.  This process, called 

“lead sulfation”, causes the crystals to become harder 

over time and more difficult to convert back to soft active 

materials. Sulfation from chronic undercharging of the bat-

tery  is  the  leading  cause  of  battery  failures  in  solar  systems.                 

In addition to reducing the battery capacity, sulfate build-up 

is the most common cause of buckling plates and cracked 

grids.  Deep cycle batteries are particularly susceptible to 

lead sulfation.
Normal charging of the battery can convert the sulfate back 

to the soft active material if the battery is fully recharged.  

However, a solar battery is seldom completely recharged, so 

the soft lead sulfate crystals harden over a period of time.  

Only a long controlled overcharge, or equalization, at a 

higher voltage can reverse the hardening of sulfate crystals.  

When to Equalize?

The ideal frequency of equalizations depends on the       

battery type (lead-calcium, lead-antimony, etc.), the depth 

of discharging, battery age, temperature, and other factors.  

One very broad guide is to equalize flooded  batteries every 

1 to 3 months or every 5 to 10 deep discharges.  Some 

batteries,  such  as  the  L-16  group,  will  need  more  frequent           

equalizations.
The difference between the highest cell and lowest cell in a 

battery can also indicate the need for an equalization. Either 

the specific gravity or the cell voltage can be measured.  

The battery manufacturer can recommend the specific   

gravity or voltage values for your particular battery. 

Preparation for Equalization

First, confirm that all of the system loads are rated for the 

equalization voltage.  Consider that at 0°C (32°F) the equal-

ization voltage will reach 16.75 volts for L-16 batteries with 

a temperature sensor installed.  Disconnect any loads at risk 

of damage due to the high input voltage.
If Hydrocaps are used, be sure to remove them before start-

ing an equalization.  Replace the Hydrocaps with standard 

battery cell caps.  The Hydrocaps can get very hot during an 

equalization.  Also, if Hydrocaps are used, the equalization 

should be set for manual only (DIP switch #7 is Off).

After the equalization is finished, add distilled water to each 

cell to replace gassing losses.  Check that the battery plates 

are covered.

Equalize a Sealed Battery?

The 

Battery Charging Settings

 table (see table 4-1 in this 

section) shows two sealed battery settings with an Equal-

ization cycles.  These are minimal “boost” cycles to level 

individual cells.  This is not an equalization, and will not vent 

gas from sealed batteries that require up to 14.4V  charg-

ing (12V battery).  Many VRLA batteries, including AGM and 

Содержание PS-MPPT-25

Страница 1: ...ation Operation and Maintenance Manual www morningstarcorp com ProStar MPPT TM MODELS PS MPPT 25 PS MPPT 25M PS MPPT 40 PS MPPT 40M MAXIMUM POWER POINT TRACKING For the most recent manual revisions se...

Страница 2: ...iguration 21 3 3 Mounting 24 3 4 Wiring 25 4 0 Operation 35 4 1 TrakStar MPPT Technology 35 4 2 Battery Charging Information 37 4 3 Load Control Information 47 4 4 LED Indications 49 4 4 1 Power up 49...

Страница 3: ...ion du contr leur solaire ProStar MPPT Les symboles suivants sont utilis s dans ce manuel pour indiquer des conditions potentiellement dangereuses ou des consignes importantes de s curit AVERTISSEMENT...

Страница 4: ...allow water to enter the controller Install the ProStar MPPT in a location that prevents casual contact The ProStar MPPT heatsink can become very hot during operation Use insulated tools when working...

Страница 5: ...with connection to the ProStar MPPT ground terminal The grounding conductor must be secured against any accidental detachment Pr cautions de S curit D installation AVERTISSEMENT L appareil n est pas f...

Страница 6: ...al regulations or codes for requirements AVERTISSEMENT Risque d Explosion Au rebut des piles est n cessaire Ne pas jeter les piles dans le feu Se r f rer aux r glementations locales ou des codes pour...

Страница 7: ...s de caoutchouc Utiliser des outils avec poign es isolantes et vitez de placer des outils ou des objets m talliques sur le dessus de batteries D brancher la source de charge avant de brancher ou dis r...

Страница 8: ...voltage sense terminals Digital meter display options Optional remote battery temperature sensor 5 year warranty see Section 6 0 2 0 GENERAL INFORMATION 2 2 Regulatory Information NOTE This section c...

Страница 9: ...ada 2 3 Versions and Ratings PS MPPT 25 Rated for maximum 25 amps continuous current battery or load Designed for 12 or 24 VDC systems PS MPPT 25M Includes metering display Rated for maximum 25 amps c...

Страница 10: ...Power connections for Load and cable terminations 7 Battery Positive and Negative Terminals Power connections for Battery and cable terminations 8 Local Temperature Sensor Compensates charging based...

Страница 11: ...perform the following tasks generator control 2 3 and 4 wire configurations dry contacts for alarms and other signals advanced load control vent fan control DIN rail compatible or surface mount Ground...

Страница 12: ...er Loose power connections and or corroded wires may result in resistive connections that melt wire insulation burn surrounding materials or even cause fire Ensure tight connections and use cable clam...

Страница 13: ...iger des cotes inf rieures que mentionn s ci dessus de mani re ne pas pour d passer n importe quel fils particulier admissible WARNING Minimum over current protection device interrupt ratings must be...

Страница 14: ...lize Equalize Interval days Equalize Interval days Equalize Interval days off off off 1 Sealed 14 00 13 50 150 off off on 2 Sealed 14 15 13 50 14 40 150 60 120 28 off on off 3 Sealed 14 30 13 50 14 60...

Страница 15: ...re 3 2 below Install in an area protected from direct rain and sun If the controller is installed in an enclosure some ventilation is recommended Do not locate in an enclosure where battery gases can...

Страница 16: ...ion or limit equalization at a lower battery voltage because the controller measures a higher voltage at the controller s ter minals than is the actual battery voltage For example if the controller is...

Страница 17: ...nd the battery will be damaged AVERTISSEMENT Endommagement de l quipement Ne placez jamais la sonde de temp rature dans un l ment de batterie Le RTS et la batterie seraient endommag s CAUTION The ProS...

Страница 18: ...trode conductor GEC to the case ground terminal The ProStar MPPT does not have internal ground fault protection but where the NEC requires the use of a ground fault protec tion device GFPD the system...

Страница 19: ...40 Volt MODULE 40 Volt MODULE 40 Volt MODULE SOLAR Solar Disconnect SOLAR 120Voc Maximum STEP 7 Load Connections see diagram below Turn the loads off and connect the load wires to the load terminals...

Страница 20: ...i mum Power Point Tracking technology to extract maximum power from the solar module s The tracking algorithm is fully automatic and does not require user adjustment Trakstar technology will track the...

Страница 21: ...but the module s Vmp is typically around 17V Figure 4 1 shows a typical current vs voltage output curve for a nominal 12V off grid module Figure 4 1 Nominal 12 volt solar module I V curve and output...

Страница 22: ...al temperature sensor or an optional Remote Temperature Sensor RTS if connected Equalization Stage WARNING Risk of Explosion Equalizing vented batteries produces explosive gases The battery bank must...

Страница 23: ...tery can convert the sulfate back to the soft active material if the battery is fully recharged However a solar battery is seldom completely recharged so the soft lead sulfate crystals harden over a p...

Страница 24: ...f 7 L 16 15 40 13 40 16 00 180 180 240 14 on on on 8 Custom Custom Custom Custom Custom Custom Custom Custom Custom Custom Custom Sealed battery type includes gel and AGM batteries Custom LVD volts LV...

Страница 25: ...rge current causing battery voltage to drop below Float voltage for 60 minutes After the load turns off the controller returns to Bulk charging and then Absorption stage once again In this example a l...

Страница 26: ...w of all loads must not exceed the ProStar MPPT 25 or 30 amp maximum load rating CAUTION Do not wire an AC inverter of any size to the load terminals of the ProStar MPPT damage to the load control cir...

Страница 27: ...load connections before applying power 4 4 LED Indications KEY G green G Y R flashing sequencially Y yellow G Y flashing together R red G Y R G and Y flashing together alternating with R flash 4 4 1...

Страница 28: ...are present the initial press will conduct a lighting test A lighting test is used to verify correct wiring in the load circuit and or verify the lighting components are operational If no faults or r...

Страница 29: ...authorized Morningstar dealer for service 4 7 Custom Settings 4 7 1 Programming with the Meter Display The ProStar MPPT is available in metered and non metered versions The metered model allows Custom...

Страница 30: ...he ProStar MPPT s meter map consists of two main axes The horizontal top level daily monitoring screens and the vertical Main Menu stacked screens The four lighted triangular directional control keys...

Страница 31: ...can be edited to specify a time offset to trigger an action which can be Do Nothing Lights On or Lights Off The combination setting of each channel will specify whether the actions and events of each...

Страница 32: ...NDER CERTAIN FAULT CONDITIONS BATTERY COULD BECOME OVER CHARGED TEST BETWEEN ALL TERMINALS AND GROUND BEFORE TOUCHING AVERTISSEMENT RISQUE DE CHOC LECTRIQUE NON ALIMENTATION OU AUX BORNES D ACCESSOIRE...

Страница 33: ...Star MPPT and then reconnect If the controller is re started with the failure still present the controller may not detect that the RTS is connected and the LEDs will not indicate a fault A metered mod...

Страница 34: ...ll stop charging and indicate a fault condi tion After all settings have been modified the controller must be reset by removing and then restoring power to the controller The new programmed settings w...

Страница 35: ...in Section 6 LIMITED WARRANTY Morningstar Solar Controllers and Inverters All of Morningstar s products with the exception of the Sure Sine 300 inverter and SHS controller are warrantied to be free f...

Страница 36: ...s deal ers system designers installers and vast online resources including the String Calculator array design tool at www morningstarcorp com are available to assist in these areas Morningstar can hel...

Страница 37: ...d before further warranty replacements can be considered for the original or future cases NOTE Please do not return units without an RMA or case number Doing so will increase the time required to reso...

Страница 38: ...f on on 4 AGM Flooded 14 40 13 50 15 10 180 120 180 28 on off off 5 Flooded 14 60 13 50 15 30 180 120 180 28 on off on 6 Flooded 14 70 13 50 15 40 180 180 240 28 on on off 7 L 16 15 40 13 40 16 00 180...

Страница 39: ...ks of Morningstar Corporation MODBUSTM and MODBUS TCP IPTM are trademarks of Modbus IDA www modbus ida org 2016 Morningstar Corporation All rights reserved MS 001537 v1 4 REACH ALL COMPONENTS COMPLIAN...

Страница 40: ...00 1050 1100 1150 Output Power Watts E ciency ProStar MPPT E ciency 24 Volt System 62 Vmp 93 Vmp APPENDIX B De rating Graphs Battery Current vs Array Voltage Vmp Array Voltage Volts Battery Current Am...

Страница 41: ...2 00 4 00 2 5 0 32 0 36 0 42 0 50 0 63 0 84 1 26 2 52 Table C 2 Maximum 1 way wire distance for 12 Volt systems solid copper 2 voltage drop 2 Voltage Drop Charts for 75 C Solid Copper Wire 1 Way Wire...

Страница 42: ...rts for 90 C Stranded Copper Wire 1 Way Wire Distance feet 12 Volt System Wire Size AWG 40A 35A 30A 25A 20A 15A 10A 5A 2 0 33 6 38 4 44 8 53 8 67 2 89 6 134 4 268 9 1 0 26 6 30 4 35 5 42 6 53 3 71 0 1...

Страница 43: ...01 6 69 10 03 20 06 10 1 58 1 80 2 10 2 52 3 15 4 21 6 31 12 62 6 0 99 1 13 1 32 1 59 1 98 2 64 3 97 7 93 4 0 62 0 71 0 83 1 00 1 25 1 66 2 50 4 99 2 5 0 39 0 45 0 52 0 63 0 78 1 05 1 57 3 14 Table C...

Отзывы: