3.0
Installation Instructions
ProStar MPPT Operator’s Manual
23
22
Switches 4, 5, 6: Battery Type Selection
Preset ProStar MPPT battery charging options are shown in
table 3-1 below. All voltage settings listed are for nominal
12 volt batteries.
Multiply the voltage settings by two (2) for 24 volt systems.
NOTE:
These settings are general guidelines for
use at the operator’s discretion. The ProStar MPPT
can be programmed to satisfy a wide range of charging param-
eters, but only the battery manufacturer can recommend optimal
settings for their products.
DIP
Switch
Settings
4-5-6
Battery
Type
Absorp.
Stage
(volts)
Float
Stage
(volts)
Equalize
Stage
(volts)
Absorp.
Time
(mins)
Equalize
Time
(mins)
Equalize
Timeout
(mins)
Equalize
Equalize
Equalize
Interval
(days)
Equalize
Interval
(days)
Equalize
Interval
(days)
off-off-off 1 - Sealed*
14.00
13.50
150
off-off-on 2 - Sealed*
14.15
13.50
14.40
150
60
120
28
off-on-off 3 - Sealed*
14.30
13.50
14.60
150
60
120
28
off-on-on 4- AGM/Flooded
14.40
13.50
15.10
180
120
180
28
on-off-off 5 - Flooded
14.60
13.50
15.30
180
120
180
28
on-off-on 6 - Flooded
14.70
13.50
15.40
180
180
240
28
on-on-off 7 - L-16
15.40
13.40
16.00
180
180
240
14
on-on-on 8 - Custom
Custom
Custom
Custom
Custom
Custom
Custom
Custom
Custom Custom
Custom
* “Sealed” battery type includes gel and AGM batteries
Custom
LVD
(volts)
LVR
(volts)
Custom
12.30
13.80
12.10
13.60
11.90
13.40
11.50
13.00
11.70
13.20
11.30
12.80
11.50
12.60
Table 3.1. Battery charging settings for each selectable battery type
Switch 7: Battery Equalization
Mode
Switch 7
Manual Equalization
OFF
Auto Equalization
ON
Switch 8: Meterbus / MODBUS Settings
Mode
Switch 8
Meterbus
OFF
MODBUS
ON