Programmable Multi-Axis Servo Drive Power Supply Unit Operation Manual
ID no.: CA97556-001 Date: 03/2015
moog
71
Appendix
Mechanical conditions
Power Supply Unit
Vibration limit in transit
as per IEC/EN 61800-2, IEC/EN 60721-3-2 class 2M1
Frequency [Hz]
Amplitude [mm (in)]
Acceleration [m/s²]
2 ≤ f < 9
3.5 (0.14)
Not applicable
9 ≤ f < 200
Not applicable
10
200 ≤ f < 500
Not applicable
15
Shock limit in transit
as per IEC/EN 61800-2, IEC/EN 60721-2-2 class 2M1
Drop height of packed device maximum 0.25 m (0.82 ft)
Vibration limits of the system
1)
as per IEC/EN 61800-2, IEC/EN 60721-3-3 class 3M1
Frequency [Hz]
Amplitude [mm (in)]
Acceleration [m/s²]
2 ≤ f < 9
0.3 (0.01)
Not applicable
9 ≤ f < 200
Not applicable
1
1) Note: The devices are only designed for stationary use.
Table A.13 Mechanical conditions – Power Supply Unit
ATTENTION!
According to EN ISO 13849-2 the cabinet must have IP54 protection or higher
when using the STO (Safe Torque OFF) safety function.
ATTENTION!
The Power Supply Unit and the Multi-Axis Servo Drives must not be installed
in areas where they are exposed to continuous shaking.
!
!
Climatic conditions
Power Supply Unit
in transit
as per IEC/EN 61800-2, IEC/EN 60721-3-2 class 2K3
1)
Temperature
-25 °C to +70 °C (-13 °F to +158 °F)
Relative humidity
95 % at m40 °C (+104 °F)
in storage
as per IEC/EN 61800-2, IEC/EN 60721-3-1 classes 1K3 and 1K4
2)
Temperature
-25 °C to +55 °C (-13 °F to +131 °F)
Relative humidity
5 to 95 %
in operation
as per IEC/EN 61800-2, IEC/EN 60721-3-3 class 3K3
3)
Temperature
-10 °C (+14 °F) to +40 °C (+104 °F), to +55 °C
(+131 °F) with power reduction (2 % per °C/°F)
Relative humidity
5 to 85 % without condensation
1) The absolute humidity is limited to maximum 60 g/m³. This means, at +70 °C (+158 °F) for example, that the relative
humidity may only be maximum 40 %.
2) The absolute humidity is limited to maximum 29 g/m³. So the maximum values for temperature and relative humidity
stipulated in the table must not occur simultaneously.
3) The absolute humidity is limited to maximum 25 g/m³. That means that the maximum values for temperature and relative
humidity stipulated in the table must not occur simultaneously.
Table A.12 Climatic conditions – Power Supply Unit