Programmable Multi-Axis Servo Drive Power Supply Unit Operation Manual
ID no.: CA97556-001 Date: 03/2015
moog
39
Electrical installation
Mains connection conditions
To ensure undisturbed operation on the supply system with a Power Supply Unit, a
minimum requirement for the short-circuit power at the mains connection applies. The
transition at the mains filter is defined as the mains connection.
The requirement must be met in order to avoid impairment at the Power Supply Unit
and interference with other devices connected in parallel to this mains connection, and
to enable a reliable operating state.
The term “short-circuit power” is a theoretical value of an apparent power occurring in a
current network when a short-circuit is caused at a transfer point.
MSD Power Supply
Short-circuit
ratio Rsc
1)
Minimum requirements for the short-circuit
power at the mains connection for undisturbed
operation
G396-026
(Sn = Pn = 26 kW)
30 ... 50
800 kVA ... 1300 kVA
G396-050
(Sn = Pn = 50 kW)
1500 kVA ... 2500 kVA
G396-075
(Sn = Pn = 75 kW)
2250 kVA ... 3750 kVA
G396-110
(Sn = Pn = 110 kW)
3300 kVA ... 5500 kVA
1) Rsc is defined as the short-circuit ratio of the short-circuit power (Sk) at the mains connection to the rated power (Sn) of
the Power Supply Unit (Rsc = Sk/Sn).
Table 3.5 Mains connection conditions
Procedure:
Define the cable cross-section depending on the maximum current and ambient temperature.
Cable cross-section according to local regulations and conditions.
Use shielded cables, as shown in Figure 3.15.
Wire the Power Supply Unit with the mains supply as shown in Figure 3.15.
Do not switch on the power!
For more information on connection of the terminal X21 precharge see section 3.6.2, p. 37.
For more information on connection of the components see section 3.15, p. 48 ff.
Technical data of components see section A.7, p. 72 ff.
ATTENTION!
If local regulations require the installation of a residual current operated
protective device, the following applies: In case of a fault the Power Supply
Unit is able to generate DC fault currents without zero crossing. The Power
Supply Unit therefore must only be operated with RCDs
1)
of type B for AC
fault currents, pulsating and smooth DC fault currents which are suitable for
servo drive operation - see IEC 60755. RCMs
2)
can additionally be used for
monitoring purposes.
1) Residual Current Protective Device
2) Residual Current Monitor
Terminal X12/L1,L2,L3
Size
Size 5
Size 6A
Device
G396-026
G396-050
G396-075
G396-110
Cable connection capacity
0.5 ... 25 mm
2
(0.0008 ... 0.04 in
2
)
(AWG 20...AWG 4)
1)
50 ... 150 mm
2
(0.08 ... 0.23 in
2
)
(10 ... 95 mm
2
(0.02 ... 0.15 in
2
))
3)
(AWG 0...
AWG 5/0)
2)
50 ... 150 mm
2
(0.08 ... 0.23 in
2
)
(AWG 0...
AWG 5/0)
2)
Tightening torque
2.5 ... 4.5 Nm
25 ... 30 Nm
1) Flexible cable with ferrule
2) Flexible cable with or without ferrule
3) With optional inserts for G396-075-xxx-xxx to reduce the diameter
1.
2.
!
Содержание G396-026
Страница 12: ...Programmable Multi Axis Servo Drive Power Supply Unit Operation Manual ID no CA97556 001 Date 03 2015 moog 12...
Страница 83: ...Programmable Multi Axis Servo Drive Power Supply Unit Operation Manual ID no CA97556 001 Date 03 2015 moog 81...
Страница 84: ...Programmable Multi Axis Servo Drive Power Supply Unit Operation Manual ID no CA97556 001 Date 03 2015 moog 82...