background image

5-565.1

17

start-uP Procedure

main burner. As the temperature drops, the voltage drops 

causing the modulating valve to open further. If the discharge 

air temperature increases, the voltage increases causing the 

modulating valve to close allowing less gas flow to the main 

burner. For further information regarding the operation of the 

electronic modulating system, consult the literature provided 

with the unit.

  8.  The unit continues to operate in this manner until the 

thermostat is satisfied, at which time both the main and pilot 

valves close 100%. (If the unit was not provided with a time 

delay relay, the blower stops at this time.)

  9.   If the unit was provided with a time delay relay, the blower 

stops after 30 to 45 seconds. 

electronic modulating gas controls

two & three furnaces - model sizes 500-960

One Master furnace is provided with up to two Slave furnaces 

that utilize electronic modulating/regulating gas controls, 

combination gas valves, ignition controls, one multiple furnace 

modulating amplifier, and either a modulating room thermostat 

or modulating duct thermostat with remote temperature adjuster. 

The thermostat controls can modulate the gas flow of all the 

furnaces between 40% through 100% full fire. The amplifier 

sends a signal to all of the gas valves so that they modulate 

at the same percentage. When the thermostat is satisfied, 

the amplifier cuts power to the combination gas valves which 

prevents gas flow to both the main and pilot burners.
When duct sensing is utilized, a room override thermostat can 

be added. When calling for heat, the room override thermostat 

provides full fire operation until the space temperature is 

satisfied. Control is then returned to the duct sensing control. 

In this situation, either the duct sensor or the room override 

thermostat can call for heat.
The sequence of operation for Electronic Modulating Gas 

Controls - Two & Three Furnaces is the same as Electronic 

Modulating Gas Controls - Single Furnace. 

 

electronic modulating gas controls -

Building management control

(0-10 vdc or 4-20 ma signal)

Utilizes an electronic modulating/regulating gas control, 

combination gas valve, an ignition control, modulating signal 

conditioner, and an inverted (0 Vdc or 4 mA being high fire and 

10 Vdc or 20 mA being low fire) 0-10 Vdc or 4-20 mA input 

signal provided by a Building Management System (BMS). 
The signal conditioner can modulate the gas flow between 40% 

through 100% full fire. When the BMS thermostat (field supplied) 

is satisfied, the BMS heat contact (field supplied) opens to cut 

power to the combination gas valve which prevents gas flow to 

both the main and pilot burners.
 1.  The BMS thermostat (field supplied) calls for heat and closes 

the BMS heat contact (field supplied).

2.  The power exhauster relay is energized starting the power 

exhauster motor. Once the motor has reached full speed, the 

differential pressure switch closes. The power exhauster relay 

pre-purge timer closes after 20 to 40 seconds energizing the 

gas control circuit. 

3.  The pilot valve opens and the spark ignitor sparks in an 

attempt to light the pilot. (If the unit was not provided with a 

time delay relay, the blower starts at this time.)

4.  Once the pilot is lit, the flame sensor proves the pilot and 

stops the spark ignitor from sparking.

5.  The main gas valve is opened and the main burner is lit to 

100% full fire.

6.  If the unit was provided with a time delay relay, the blower 

starts after 30 to 45 seconds.

7.  The modulating gas valve is controlled by the BMS 

thermostat.  The thermostat can modulate the firing rate 

between 40% through 100% full fire by modulating the 

input signal between either 0-10 Vdc or 4-20 mA (The 

signal conditioner can accept a 0-10 Vdc signal when all 

the dip switches are in the “OFF” position and 4-20 mA 

signal when all the dip switches are in the “ON” position). 

The signal conditioner converts the input signal into a DC 

voltage (0 to 12 volts DC with 0 volts high fire and 12 volts 

low fire). The output voltage is applied to the modulating 

gas valve to control the gas flow to the main burner. As the 

temperature drops, the voltage drops causing the modulating 

valve to open further.  If the discharge air temperature 

increases, the voltage increases causing the modulating 

valve to close allowing less gas flow to the main burner. For 

further information regarding the operation of the electronic 

modulating system, consult the literature provided with the 

unit.

8.  The unit continues to operate in this manner until the 

thermostat is satisfied, at which time the BMS heat contact 

opens resulting in both the main and pilot valves closing 

100%. (If the unit was not provided with a time delay relay, 

the blower stops at this time.)

9.  If the unit was provided with a time delay relay, the blower 

stops after 30 to 45 seconds.

variable air movement applications

Units may be supplied with variable frequency drives for 

applications where variable air volume is required. The minimum 

air flow may be varied between 30 and 100% of the full speed 

air flow depending on the controls selection of the unit. Due to the 

extra restrictions of the controller all selections must be performed 

with the AccuSpec configuration software. Within AccuSpec, three 

variable frequency drive speed control changeover options are 

available:
  1.  Two speed which may be controlled by a manual high/low 

switch which may be factory mounted on the control panel or 

shipped loose for field installation or by exhaust fan   

 

interlocks.

  2.  Floating building pressure sensing which utilizes a photohelic  

pressure controller to adjust the building pressure by  

 

varying the amount of makeup air supplied to the the space.

  3.  Building management control which allows for an external 

signal of 0-10VDC of 4-20mA to adjust the unit airflow.

Additionally, when the air mover supplied by others can provide 

variable air movement (i.e. 2-speed or variable frequency drive 

units), the allowable minimum CFM of the duct furnace can 

be 66% of the minimum listed CFM in Table 26.1 if the unit is 

applied as follows:
  1.  The unit is provided with 2-stage, mechanical modulation, 

or electronic modulating gas controls. (see Model 

Identification).

  2.  The unit is provided with a factory installed discharge air 

controller.

  3.  The system does not include a room thermostat.
The factory installed discharge air thermostat will prevent the 

unit from firing above the allowable 100°F rise when the unit is 

at or above the minimum CFM by monitoring the discharge air 

and going to low fire. A room thermostat, because it is located 

remote from the unit, could cause the unit to over-fire.

Содержание DBP

Страница 1: ...LEAVE THE JOB FOR YOUR SAFETY The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous FOR YOUR SAFETY if you smell gas...

Страница 2: ...a temperature rating of at least 105 C 12 When servicing or repairing this equipment use only factory approved service replacement parts A complete replacement parts list may be obtained by contacting...

Страница 3: ...led in tightly sealed buildings or confined spaces must be provided with two permanent openings one near the top of the confined space and one near the bottom Each opening should have a free area of n...

Страница 4: ...uspension or floor mounting is adequate to support the weight of the unit see Weights for base unit and factory installed option weights For proper operation the unit must be installed in a level hori...

Страница 5: ...See Figure 5 3 Provide an airtight seal between the ductwork and the unit Seams with cracks in the ductwork should be caulked and or taped and be of permanent type All duct connections MUST be airtigh...

Страница 6: ...orm with local building codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 Latest Edition In Canada installation must be in accordance with CAN CGA B149 1 for n...

Страница 7: ...e to the inability to verify complete seal of inner pipes 12 MIN RECOMMENDED 4 MIN TEE WITH DRIP LEG AND CLEANOUT CAP SLOPE 1 4 PER FOOT DOWNWARD TOWARD DRIP LEG EXHAUST H MIN 12 MIN RECOMMENDED 4 MIN...

Страница 8: ...gged tapping accessible for test gauge connection See Figure 8 1 Verify the manual shut off valve is gas tight on an annual basis 4 Provide a sediment trap before each unit in the line where low spots...

Страница 9: ...onal drawings on Figures 43 1 through 44 1 for the electrical knock out locations 9 All supply power electrical connections are made in the electrical section of the unit The low voltage thermostat an...

Страница 10: ...ction line is allowed to be cooled liquid will condense in the line and can severely damage the compressor If the liquid line is warmed the refrigerant can flash into a gas This will cause erratic ope...

Страница 11: ...uid Piping 1 Once installed the coil should be pressurized to 100 psig with dry nitrogen or other suitable gas The coil should be left pressurized for a minimum of 10 minutes If the coil holds the pre...

Страница 12: ...ibited glycol solution that will protect the coil from the lowest possible temperatures that can occur at the particular coil s locality Start Up Procedure 1 Turn off power to the unit at the disconne...

Страница 13: ...justment The gas pressure regulator integral to the combination gas control is adjusted at the factory for average gas conditions It is important that gas be supplied to the duct furnace in accordance...

Страница 14: ...cause yellow tipping Retighten set screws after adjustment Propane Gas Flame Control An optimum flame will show a slight yellow tip Prior to flame adjustment operate furnace for at least fifteen minu...

Страница 15: ...ge is disconnected and the damper closed Before operating the unit the fresh and return air dampers must be connected This is accomplished by the following 1 The damper actuator should be de energized...

Страница 16: ...rt stop switch 2 The power exhauster relay is energized starting the power exhauster motor Once the motor has reached full speed the differential pressure switch closes The power exhauster relay pre p...

Страница 17: ...the flame sensor proves the pilot and stops the spark ignitor from sparking 5 The main gas valve is opened and the main burner is lit to 100 full fire 6 If the unit was provided with a time delay rela...

Страница 18: ...Adjuster Capillary 45 43 40 38 36 34 Units with Premium Control Box 32 30 9 46 48 12 13 10 50 49 52 51 55 47 4 6 5 1 2 3 8 27 25 23 21 19 17 15 16 18 20 22 24 26 14 44 42 39 37 35 33 31 1 Discharge T...

Страница 19: ...e set to insure that the minimum inlet gas pressure is available 6 W C for natural gas 11 W C for propane gas Figure 19 4 Low or High Gas Pressure Switch 3 High Gas Pressure Switch OPT The high gas pr...

Страница 20: ...controls damper actuator motor starter etc Refer to the unit model number to determine the volt amp VA capacity of the duct furnace The 15th digit indicates the VA See Model Nomenclature 14 Control Re...

Страница 21: ...tory installed in the blower section The fresh air damper is used as an outside air shut off damper so ultra low leak Class II leakage resistance less than 10 CFM ft2 at 1 W C dampers with self compen...

Страница 22: ...reduce compressor operation of the mechanical cooling system The economizer functions as a true first stage of cooling and provides maximum fuel economy during the cooling cycle An enthalpy sensor is...

Страница 23: ...115V 1Ph power supply must be routed through the electrical section wall into the back of the convenience outlet junction box 38 Blower Door Switch OPT The blower door switch is factory installed ins...

Страница 24: ...the set point The controller includes a set point dial that must be field set to the desired mixed air temperature typically 55 F 43 Warm Up Stat OPT A warm up stat is provided with Air Control optio...

Страница 25: ...re of the blower motor blockage of the inlet air etc the manual reset switch prevents the unit from cycling on the high limit If the limit temperature is exceeded a service person must inspect the uni...

Страница 26: ...G or H I J or K E or F G or H I J or K Max Temp Rise F 100 100 100 100 100 100 100 100 100 Min Temp Rise F 37 31 20 45 37 22 52 42 25 Max CFM 6000 7250 11111 5700 7000 12000 5700 7000 12000 Min CFM 2...

Страница 27: ...8 4558 4233 3951 3704 3486 3292 3119 2963 Btu Hr Air Temperature Rise through Unit F Input Output 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 Max CFM Min 500 000 400 000 9259 8230 7407 673...

Страница 28: ...ct an indirect fired 100 make up air unit to meet the following conditions 1 CFM at sea level 5 000 cfm 2 Outdoor design temp 10 F Indoor design temp 70 F 3 Heating output capacity 5000 cfm x 70 F 10...

Страница 29: ...or I J H blowers Using 5000 cfm and 0 87 W C T S P the horsepower is 3hp and 700 rpm Although I J H blowers results in a 3 hp motor this blower requires the use of the extended cabinet length As a res...

Страница 30: ...0 15 0 02 0 07 0 02 2000 0 03 0 03 0 05 0 06 0 03 0 11 0 06 0 17 0 02 0 08 0 02 2500 0 04 0 04 0 07 0 09 0 04 0 15 0 09 0 24 0 03 0 09 0 03 3000 0 05 0 06 0 10 0 11 0 06 0 19 0 13 0 32 0 04 0 12 0 04...

Страница 31: ...3400 1 35 804 1 55 881 1 77 955 2 00 1025 2 23 1092 2 47 1157 2 96 1280 3 49 1396 4 03 1505 3800 1 82 880 2 05 951 2 29 1018 2 53 1083 2 79 1146 3 04 1206 3 58 1322 4 14 1431 4 72 1535 4200 2 40 959 2...

Страница 32: ...10 00 1167 9259 6 40 804 6 91 846 7 45 887 7 99 927 8 55 966 9 12 1004 10 30 1079 11 52 1150 12 79 1218 10000 7 97 862 8 52 901 9 09 939 9 67 977 10 27 1014 10 87 1050 12 12 1120 13 41 1187 14 74 125...

Страница 33: ...69 1236 115 F 4500 1 68 708 1 98 780 2 30 847 2 63 912 2 98 973 3 34 1032 4 11 1142 4 94 1245 105 F 120 F 4938 2 15 763 2 48 89 2 82 893 3 17 953 3 54 1011 3 93 1066 4 74 1172 104 F 119 F 5000 2 23 77...

Страница 34: ...used on units that include a blower The Sheave Arrangement is Digit 19 and is found on the unit Model Identification Plate The Sheave Assembly describes the motor and blower sheave size and bore as w...

Страница 35: ...Assembly Digit 19 Sheave Assembly Digit 19 SheaveAssembly 56 A 3H35129B1 D 3H35129B4 143 or 145 B 3H35129B2 E 3H35129B5 H 3H35129B8 182 to 184 C 3H35129B3 F 3H35129B6 I 3H35129B9 K 3H35129B11 O 3H3512...

Страница 36: ...410 3H35128B4 6 771 751 731 710 690 670 649 629 609 589 568 3H35128B7 9 958 939 920 901 882 863 843 824 805 786 767 3H35128B10 12 1136 1116 1096 1076 1055 1035 1015 994 974 954 934 3H35128B13 14 1380...

Страница 37: ...Diameter Bore Pitch Diameter Bore 3H35129B1 4 1 0 625 10 9 1 B71 3H35129B2 4 1 0 875 10 9 1 B71 3H35129B3 4 1 1 125 10 9 1 B70 3H35129B4 4 7 0 625 10 9 1 BX71 3H35129B5 4 7 0 875 10 9 1 BX71 3H35129B6...

Страница 38: ...Thermal Weight Efficiency 17 18 Size HP Type Size Draw Factor Overload lbs A1 1 3 ODP 56 3 0 1 35 Yes 25 N A B1 1 2 ODP 56 4 1 1 20 Yes 23 N A B5 1 2 TEFC 56 4 0 1 15 Yes 28 N A C1 3 4 ODP 56 5 5 1 25...

Страница 39: ...15 66 86 5 F7 or R7 2 TEFC 18 9 145T 6 4 2 5 1 00 41 84 0 70 0 F8 or R8 2 TE 18 12 182T 6 4 3 9 1 15 65 84 0 77 0 G1 or S1 3 ODP 182T 10 0 1 15 78 81 5 G2 or S2 3 ODP HE 182T 8 9 1 15 83 89 5 G3 or S...

Страница 40: ...9 5 G7 or S7 3 TE 18 9 182T 10 0 3 6 1 00 64 84 0 70 0 G8 or S8 3 TE 18 12 184T 8 8 5 5 1 15 84 84 0 82 0 H1 or T1 5 ODP 184T 14 0 1 15 87 87 5 H2 or T2 5 ODP HE 184T 13 6 1 15 94 89 5 H3 or T3 5 ODP...

Страница 41: ...4 0 70 0 G8 or S8 3 TE 18 12 184T 4 3 2 6 1 15 73 82 5 75 5 H1 or T1 5 ODP 184T 7 0 1 15 87 87 5 H2 or T2 5 ODP HE 184T 6 8 1 15 94 89 5 H3 or T3 5 ODP 18 9 184T 9 1 3 2 1 15 94 84 0 73 0 H4 or T4 5 O...

Страница 42: ...DP 184T 5 2 1 15 91 87 5 H5 or T5 5 TEFC 184T 5 2 1 15 89 87 5 H6 or T6 5 TE HE 184T 5 2 1 15 117 89 5 I1 or W1 7 1 2 ODP 213T 7 8 1 15 113 88 5 I5 or W5 7 1 2 TEFC 213T 8 0 1 15 142 89 0 I6 or W6 7 1...

Страница 43: ...7 27 13 32 75 30 00 28 00 29 96 43 23 44 05 42 37 24 60 8 10 44 80 87 77 3 4 350 400 E F G or H 1 37 75 23 07 38 63 32 75 42 00 28 00 41 90 43 23 55 57 42 37 36 14 10 44 80 87 77 3 4 500 600 G or H 2...

Страница 44: ...1 24 00 4 35 34 00 50 37 1 98 2 00 2 00 2 00 P 1 36 32 54 D 19 23 30 5 HEIGHT X E WIDTH 7 65 30 48 152 83 Figure 44 2 DCP Indoor Power Vented Cooling Package Unit Dimensions with Blower Type I J K or...

Страница 45: ...81 55 41 7 00 Dimensions Table 45 2 Indoor Power Vented Cooling Package Units All dimensions in inches Model Blower Type Size Digit 16 A B C D E N K L J M 75 All 87 77 34 85 81 30 19 52 32 00 6 23 10...

Страница 46: ...Qty 75 All 27 5 30 5 1 5 18 25 21 1 1 625 1 1 375 16 25 26 5 19 25 2 1 625 2 0 875 100 125 All 27 5 30 5 1 5 21 28 24 1 1 625 1 1 375 19 5 29 75 22 5 2 1 625 2 0 875 150 175 All 27 5 30 5 1 5 24 31 2...

Страница 47: ...nsulation All Sections 75 All 343 6 26 46 10 72 100 125 All 382 6 26 46 10 72 150 175 All 423 6 29 52 10 77 200 225 All 491 6 29 52 12 85 250 300 E F G or H 526 8 33 60 12 87 250 300 I J or K 775 15 3...

Страница 48: ...gas and electric supply 2 Disconnect gas manifold at ground union joint 3 Remove the two screws holding the manifold to the heat exchanger support 4 Slide the manifold through the manifold bracket 5...

Страница 49: ...urner assembly out The pilot is attached to the burner assembly 6 Examine the burner and pilot assembly for cleanliness and or obstructions as necessary see Duct Furnace for cleaning instructions 7 Re...

Страница 50: ...if necessary 9 Find source and re direct airflow away from unit 10 Tighten pilot orifice Flame impingment on pilot sensor may cause pilot sensor to become inoperative Main burners do not light Pilot...

Страница 51: ...thermostat 5 Check unit wiring against the wiring diagram 6 Check design conditions If unit is undersized an additional unit s or other heat source must be added Too Much Heat 1 Thermostat malfunctio...

Страница 52: ...fy the complete model including blower and cooling sections Ordering When servicing repairing or replacing parts on these units locate the model identification plate of the unit and always give the co...

Страница 53: ...nations 01 10 201 01 02 1000 MOTOR VENDOR CODE 01 Century 15 Marathon etc FAN OR BLOWER VENDOR CODE 10 Lau 20 Morrison etc SERIES IDENTITY NUMBER Identifies which series of controls were furnished on...

Страница 54: ...____ V L3 ______ V 22 Motor amps L1 ______ Amp L2 ______ Amp L3 ______ Amp 23 High temperature limit control continuity checked _____ Yes ____ No 24 Burner light off Low Fire Does entire burner light...

Страница 55: ...der Bearings I 18 18 Spider Bearings under 15 Hp D 9 9 Pillow Block Bearings J 18 18 Pillow Block Bearings under 15 Hp E 12 12 Spider Bearings K 18 18PillowBlockBearingsfor15Hp up F 12 12 Pillow Block...

Страница 56: ...YEARS FROM DATE OF SHIPMENT FROM SELLER These warranties are issued only to the original owner user and cannot be transferred or assigned No provision is made in these warranties for any labor allowa...

Отзывы: