background image

5-565.1

29

10. determine the supply voltage:
 

From item #9 listed above, the 460V/60Hz/3Ph results in the 

Supply Voltage = F.

11.  determine the transformer:
 

For DBP/DCP models, a 75VA Transformer is required.   

Thus, the Transformer = 2.

12. determine the Blower size and Bearing type:
 

Using Table 26.1, the Model Size 400 has three available 

blowers for which the performance tables are shown on 

pages 30-33. Since all of the blower performance curves 

can provide the required 5000 cfm, the total static pressure 

must be determined.

A)  The Pressure Drop of an option or accessory is 

determined by entering the right of the table at the 

desired cfm and reading up the table until the cfm 

intersects the desired item. For this example, in table 

30.1 the 2'' Permanent Filter line is used. At the point of 

intersection, read across the table to the left and read the 

pressure drop, in inches of water column for the filters. 

For this example, the pressure drop is 0.06'' W.C.   

As a result: 

 

For the Model Size 400 with Digit 16 = E,F,G, or H: 

2'' Permanent Filters: 

0.06" W.C. 

Internal Static Pressure Drop 

0.06" W.C.

 

The Total Static Pressure for the system is determined by 

Internal External Static = Total Static Pressure

 

For this example 0.06'' + 0.65'' = 0.71'' W.C. T.S.P.

 

From page 30,

 

for the Model Size 400 with Digit 16 = I, J, or K:

 

2'' Permanent Filters: 

0.04'' W.C.

 

Internal Static Pressure Drop 

0.04'' W.C.

 

The Total Static Pressure for the system is determined by 

Internal External Static = Total Static Pressure

 

For this example 0.04'' + 0.65'' = 0.69'' W.C. T.S.P.

B)  Using the total static pressure (T.S.P.) calculated in step 

12a, use blower performance tables for the Model Size 

400 (Table 32.1). 

 

Using Table 32.1, enter the table at the required 5000 

cfm for E, F blowers, and follow the cfm line up the 

right until it intersects with the T.S.P. line of 0.75'' W.C. 

which is shown at the top of the table. At the point of 

intersection of these two columns, read the required 

horsepower and blower rpm. Repeat this process for 

1.00”T.S.P. and literate to determine the BHP and rpm for 

0.89” W.C. For this example the horsepower is 5 and the 
blower rpm is 1280.

 

Following this procedure for G,H blowers (Using 5000 

cfm and 0.89'' W.C. T.S.P), the horsepower is 5 hp and 

920 rpm. Following this procedure for I,J,H blowers 

(Using 5000 cfm and 0.87'' W.C. T.S.P), the horsepower 

is 3hp and 700 rpm. Although I,J,H blowers results in a  

3 hp motor, this blower requires the use of the extended 

cabinet length. As a result, for purposes of this selection 

example G,H will be used.

 

Since the Bearing Type was not specified, the standard 

spider bearings will be used. Thus, using Table 32.1 with 

spider bearings, the Blower Size and Bearing Type = G.

13. determine the motor Horsepower:
 

The motor horsepower determined in step 12 was a 3 Hp.  

Since the supply voltage is 460V/60Hz/3Ph, a motor starter 

will need to be provided either with the unit or by others. For 

purposes of this selection, a motor starter by others will be 
used so the Motor Horsepower = G.

14. determine the motor type:
 

The motor type was not specified so for purposes of this 

selection the standard open drip proof motor will be used so 
the Motor Type = 1.

15. determine the sheave arrangement:
 

To establish the Sheave Arrangement, the motor frame size 

must be determined. The Motor Data tables on pages 38 to 
42 contain the motor frame size.

 

A)  Using the Supply Voltage (460V/60Hz/3Ph), enter the 

correct Motor Data table (Table 41.1). Using Model 

Nomenclature Digits 17 and 18 (G1) determined in steps 
13 and 14, find the motor frame size (182T).

B)  Using the Motor Frame Size enter the Sheave Selection 

table for the selected blower determined by step 13 

(Table 35.2). Using the rpm calculated in step 12  

(870 rpm), select the sheave range that contains the 

required rpm. Find the intersection with the Motor 

Frame Size to determine the Sheave Selection. For this 

example with a 182T frame with 870 rpm, from Table 

35.2, the Sheave Arrangement = I.

16. determine the air control:
 

The Air Control option is selected based on the required 

damper configuration. The available damper selections are 

detailed on page 21. For this selection, a 100% fresh air unit 
without return air was required so the Air Control = DA.

17. determine the evaporative cooler:
 

An evaporative cooler is not available, so for purposes of 
this selection the Evaporative Cooler = 0.

18. determine the cooling coil:
 

A cooling coil cabinet was not specified so for purposes of 

this selection the Cooling Coil = 0.

Based on the previous steps, the model number for the base 
unit is the following:

DBP400SMRLN40F2GG1IDA00

Once the basic model has been determined, the additional 

options and accessories outlined on page 18 to 25 can be 

added to the unit.

unit selection

Содержание DBP

Страница 1: ...LEAVE THE JOB FOR YOUR SAFETY The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous FOR YOUR SAFETY if you smell gas...

Страница 2: ...a temperature rating of at least 105 C 12 When servicing or repairing this equipment use only factory approved service replacement parts A complete replacement parts list may be obtained by contacting...

Страница 3: ...led in tightly sealed buildings or confined spaces must be provided with two permanent openings one near the top of the confined space and one near the bottom Each opening should have a free area of n...

Страница 4: ...uspension or floor mounting is adequate to support the weight of the unit see Weights for base unit and factory installed option weights For proper operation the unit must be installed in a level hori...

Страница 5: ...See Figure 5 3 Provide an airtight seal between the ductwork and the unit Seams with cracks in the ductwork should be caulked and or taped and be of permanent type All duct connections MUST be airtigh...

Страница 6: ...orm with local building codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 Latest Edition In Canada installation must be in accordance with CAN CGA B149 1 for n...

Страница 7: ...e to the inability to verify complete seal of inner pipes 12 MIN RECOMMENDED 4 MIN TEE WITH DRIP LEG AND CLEANOUT CAP SLOPE 1 4 PER FOOT DOWNWARD TOWARD DRIP LEG EXHAUST H MIN 12 MIN RECOMMENDED 4 MIN...

Страница 8: ...gged tapping accessible for test gauge connection See Figure 8 1 Verify the manual shut off valve is gas tight on an annual basis 4 Provide a sediment trap before each unit in the line where low spots...

Страница 9: ...onal drawings on Figures 43 1 through 44 1 for the electrical knock out locations 9 All supply power electrical connections are made in the electrical section of the unit The low voltage thermostat an...

Страница 10: ...ction line is allowed to be cooled liquid will condense in the line and can severely damage the compressor If the liquid line is warmed the refrigerant can flash into a gas This will cause erratic ope...

Страница 11: ...uid Piping 1 Once installed the coil should be pressurized to 100 psig with dry nitrogen or other suitable gas The coil should be left pressurized for a minimum of 10 minutes If the coil holds the pre...

Страница 12: ...ibited glycol solution that will protect the coil from the lowest possible temperatures that can occur at the particular coil s locality Start Up Procedure 1 Turn off power to the unit at the disconne...

Страница 13: ...justment The gas pressure regulator integral to the combination gas control is adjusted at the factory for average gas conditions It is important that gas be supplied to the duct furnace in accordance...

Страница 14: ...cause yellow tipping Retighten set screws after adjustment Propane Gas Flame Control An optimum flame will show a slight yellow tip Prior to flame adjustment operate furnace for at least fifteen minu...

Страница 15: ...ge is disconnected and the damper closed Before operating the unit the fresh and return air dampers must be connected This is accomplished by the following 1 The damper actuator should be de energized...

Страница 16: ...rt stop switch 2 The power exhauster relay is energized starting the power exhauster motor Once the motor has reached full speed the differential pressure switch closes The power exhauster relay pre p...

Страница 17: ...the flame sensor proves the pilot and stops the spark ignitor from sparking 5 The main gas valve is opened and the main burner is lit to 100 full fire 6 If the unit was provided with a time delay rela...

Страница 18: ...Adjuster Capillary 45 43 40 38 36 34 Units with Premium Control Box 32 30 9 46 48 12 13 10 50 49 52 51 55 47 4 6 5 1 2 3 8 27 25 23 21 19 17 15 16 18 20 22 24 26 14 44 42 39 37 35 33 31 1 Discharge T...

Страница 19: ...e set to insure that the minimum inlet gas pressure is available 6 W C for natural gas 11 W C for propane gas Figure 19 4 Low or High Gas Pressure Switch 3 High Gas Pressure Switch OPT The high gas pr...

Страница 20: ...controls damper actuator motor starter etc Refer to the unit model number to determine the volt amp VA capacity of the duct furnace The 15th digit indicates the VA See Model Nomenclature 14 Control Re...

Страница 21: ...tory installed in the blower section The fresh air damper is used as an outside air shut off damper so ultra low leak Class II leakage resistance less than 10 CFM ft2 at 1 W C dampers with self compen...

Страница 22: ...reduce compressor operation of the mechanical cooling system The economizer functions as a true first stage of cooling and provides maximum fuel economy during the cooling cycle An enthalpy sensor is...

Страница 23: ...115V 1Ph power supply must be routed through the electrical section wall into the back of the convenience outlet junction box 38 Blower Door Switch OPT The blower door switch is factory installed ins...

Страница 24: ...the set point The controller includes a set point dial that must be field set to the desired mixed air temperature typically 55 F 43 Warm Up Stat OPT A warm up stat is provided with Air Control optio...

Страница 25: ...re of the blower motor blockage of the inlet air etc the manual reset switch prevents the unit from cycling on the high limit If the limit temperature is exceeded a service person must inspect the uni...

Страница 26: ...G or H I J or K E or F G or H I J or K Max Temp Rise F 100 100 100 100 100 100 100 100 100 Min Temp Rise F 37 31 20 45 37 22 52 42 25 Max CFM 6000 7250 11111 5700 7000 12000 5700 7000 12000 Min CFM 2...

Страница 27: ...8 4558 4233 3951 3704 3486 3292 3119 2963 Btu Hr Air Temperature Rise through Unit F Input Output 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 Max CFM Min 500 000 400 000 9259 8230 7407 673...

Страница 28: ...ct an indirect fired 100 make up air unit to meet the following conditions 1 CFM at sea level 5 000 cfm 2 Outdoor design temp 10 F Indoor design temp 70 F 3 Heating output capacity 5000 cfm x 70 F 10...

Страница 29: ...or I J H blowers Using 5000 cfm and 0 87 W C T S P the horsepower is 3hp and 700 rpm Although I J H blowers results in a 3 hp motor this blower requires the use of the extended cabinet length As a res...

Страница 30: ...0 15 0 02 0 07 0 02 2000 0 03 0 03 0 05 0 06 0 03 0 11 0 06 0 17 0 02 0 08 0 02 2500 0 04 0 04 0 07 0 09 0 04 0 15 0 09 0 24 0 03 0 09 0 03 3000 0 05 0 06 0 10 0 11 0 06 0 19 0 13 0 32 0 04 0 12 0 04...

Страница 31: ...3400 1 35 804 1 55 881 1 77 955 2 00 1025 2 23 1092 2 47 1157 2 96 1280 3 49 1396 4 03 1505 3800 1 82 880 2 05 951 2 29 1018 2 53 1083 2 79 1146 3 04 1206 3 58 1322 4 14 1431 4 72 1535 4200 2 40 959 2...

Страница 32: ...10 00 1167 9259 6 40 804 6 91 846 7 45 887 7 99 927 8 55 966 9 12 1004 10 30 1079 11 52 1150 12 79 1218 10000 7 97 862 8 52 901 9 09 939 9 67 977 10 27 1014 10 87 1050 12 12 1120 13 41 1187 14 74 125...

Страница 33: ...69 1236 115 F 4500 1 68 708 1 98 780 2 30 847 2 63 912 2 98 973 3 34 1032 4 11 1142 4 94 1245 105 F 120 F 4938 2 15 763 2 48 89 2 82 893 3 17 953 3 54 1011 3 93 1066 4 74 1172 104 F 119 F 5000 2 23 77...

Страница 34: ...used on units that include a blower The Sheave Arrangement is Digit 19 and is found on the unit Model Identification Plate The Sheave Assembly describes the motor and blower sheave size and bore as w...

Страница 35: ...Assembly Digit 19 Sheave Assembly Digit 19 SheaveAssembly 56 A 3H35129B1 D 3H35129B4 143 or 145 B 3H35129B2 E 3H35129B5 H 3H35129B8 182 to 184 C 3H35129B3 F 3H35129B6 I 3H35129B9 K 3H35129B11 O 3H3512...

Страница 36: ...410 3H35128B4 6 771 751 731 710 690 670 649 629 609 589 568 3H35128B7 9 958 939 920 901 882 863 843 824 805 786 767 3H35128B10 12 1136 1116 1096 1076 1055 1035 1015 994 974 954 934 3H35128B13 14 1380...

Страница 37: ...Diameter Bore Pitch Diameter Bore 3H35129B1 4 1 0 625 10 9 1 B71 3H35129B2 4 1 0 875 10 9 1 B71 3H35129B3 4 1 1 125 10 9 1 B70 3H35129B4 4 7 0 625 10 9 1 BX71 3H35129B5 4 7 0 875 10 9 1 BX71 3H35129B6...

Страница 38: ...Thermal Weight Efficiency 17 18 Size HP Type Size Draw Factor Overload lbs A1 1 3 ODP 56 3 0 1 35 Yes 25 N A B1 1 2 ODP 56 4 1 1 20 Yes 23 N A B5 1 2 TEFC 56 4 0 1 15 Yes 28 N A C1 3 4 ODP 56 5 5 1 25...

Страница 39: ...15 66 86 5 F7 or R7 2 TEFC 18 9 145T 6 4 2 5 1 00 41 84 0 70 0 F8 or R8 2 TE 18 12 182T 6 4 3 9 1 15 65 84 0 77 0 G1 or S1 3 ODP 182T 10 0 1 15 78 81 5 G2 or S2 3 ODP HE 182T 8 9 1 15 83 89 5 G3 or S...

Страница 40: ...9 5 G7 or S7 3 TE 18 9 182T 10 0 3 6 1 00 64 84 0 70 0 G8 or S8 3 TE 18 12 184T 8 8 5 5 1 15 84 84 0 82 0 H1 or T1 5 ODP 184T 14 0 1 15 87 87 5 H2 or T2 5 ODP HE 184T 13 6 1 15 94 89 5 H3 or T3 5 ODP...

Страница 41: ...4 0 70 0 G8 or S8 3 TE 18 12 184T 4 3 2 6 1 15 73 82 5 75 5 H1 or T1 5 ODP 184T 7 0 1 15 87 87 5 H2 or T2 5 ODP HE 184T 6 8 1 15 94 89 5 H3 or T3 5 ODP 18 9 184T 9 1 3 2 1 15 94 84 0 73 0 H4 or T4 5 O...

Страница 42: ...DP 184T 5 2 1 15 91 87 5 H5 or T5 5 TEFC 184T 5 2 1 15 89 87 5 H6 or T6 5 TE HE 184T 5 2 1 15 117 89 5 I1 or W1 7 1 2 ODP 213T 7 8 1 15 113 88 5 I5 or W5 7 1 2 TEFC 213T 8 0 1 15 142 89 0 I6 or W6 7 1...

Страница 43: ...7 27 13 32 75 30 00 28 00 29 96 43 23 44 05 42 37 24 60 8 10 44 80 87 77 3 4 350 400 E F G or H 1 37 75 23 07 38 63 32 75 42 00 28 00 41 90 43 23 55 57 42 37 36 14 10 44 80 87 77 3 4 500 600 G or H 2...

Страница 44: ...1 24 00 4 35 34 00 50 37 1 98 2 00 2 00 2 00 P 1 36 32 54 D 19 23 30 5 HEIGHT X E WIDTH 7 65 30 48 152 83 Figure 44 2 DCP Indoor Power Vented Cooling Package Unit Dimensions with Blower Type I J K or...

Страница 45: ...81 55 41 7 00 Dimensions Table 45 2 Indoor Power Vented Cooling Package Units All dimensions in inches Model Blower Type Size Digit 16 A B C D E N K L J M 75 All 87 77 34 85 81 30 19 52 32 00 6 23 10...

Страница 46: ...Qty 75 All 27 5 30 5 1 5 18 25 21 1 1 625 1 1 375 16 25 26 5 19 25 2 1 625 2 0 875 100 125 All 27 5 30 5 1 5 21 28 24 1 1 625 1 1 375 19 5 29 75 22 5 2 1 625 2 0 875 150 175 All 27 5 30 5 1 5 24 31 2...

Страница 47: ...nsulation All Sections 75 All 343 6 26 46 10 72 100 125 All 382 6 26 46 10 72 150 175 All 423 6 29 52 10 77 200 225 All 491 6 29 52 12 85 250 300 E F G or H 526 8 33 60 12 87 250 300 I J or K 775 15 3...

Страница 48: ...gas and electric supply 2 Disconnect gas manifold at ground union joint 3 Remove the two screws holding the manifold to the heat exchanger support 4 Slide the manifold through the manifold bracket 5...

Страница 49: ...urner assembly out The pilot is attached to the burner assembly 6 Examine the burner and pilot assembly for cleanliness and or obstructions as necessary see Duct Furnace for cleaning instructions 7 Re...

Страница 50: ...if necessary 9 Find source and re direct airflow away from unit 10 Tighten pilot orifice Flame impingment on pilot sensor may cause pilot sensor to become inoperative Main burners do not light Pilot...

Страница 51: ...thermostat 5 Check unit wiring against the wiring diagram 6 Check design conditions If unit is undersized an additional unit s or other heat source must be added Too Much Heat 1 Thermostat malfunctio...

Страница 52: ...fy the complete model including blower and cooling sections Ordering When servicing repairing or replacing parts on these units locate the model identification plate of the unit and always give the co...

Страница 53: ...nations 01 10 201 01 02 1000 MOTOR VENDOR CODE 01 Century 15 Marathon etc FAN OR BLOWER VENDOR CODE 10 Lau 20 Morrison etc SERIES IDENTITY NUMBER Identifies which series of controls were furnished on...

Страница 54: ...____ V L3 ______ V 22 Motor amps L1 ______ Amp L2 ______ Amp L3 ______ Amp 23 High temperature limit control continuity checked _____ Yes ____ No 24 Burner light off Low Fire Does entire burner light...

Страница 55: ...der Bearings I 18 18 Spider Bearings under 15 Hp D 9 9 Pillow Block Bearings J 18 18 Pillow Block Bearings under 15 Hp E 12 12 Spider Bearings K 18 18PillowBlockBearingsfor15Hp up F 12 12 Pillow Block...

Страница 56: ...YEARS FROM DATE OF SHIPMENT FROM SELLER These warranties are issued only to the original owner user and cannot be transferred or assigned No provision is made in these warranties for any labor allowa...

Отзывы: