ALL INSTALLATIONS AND SERVICE MUST BE PERFORMED BY QUALIFIED SERVICE PERSONNEL.

 

 

 

CONCENTRIC VENT / COMBUSTION AIR KIT FOR  

SIDEWALL OR VERTICAL VENTING APPLICATIONS 

  

 

ELECTRIC SHOCK HAZARD/FIRE AND/OR EXPLOSION HAZARD. 

 
Failure to carefully read and follow all instructions in these instructions could result in death, 
personal injury, property damage and/or furnace malfunction. 
 
Installation or repairs made by unqualified persons could result in hazards to you and others. 
Installation MUST conform with local codes or, in the absence of local codes, with codes of the 
country having jurisdiction. 
 
The information contained in these instructions is intended for use by a qualified service 
technician familiar with safety procedures and equipped with the proper tools and test 
instruments.

 

  

 

ELECTRIC SHOCK HAZARD/FIRE AND/OR EXPLOSION HAZARD. 

 
Failure to follow this warning could result in death, personal injury, property damage and/or 
equipment damage. 
 
Turn OFF gas supply at manual gas valve before turning OFF electric power supply and 
starting installation. 
 
Turn OFF electric power supply at disconnect switch or service panel before starting 
installation.

 

  

 

CARBON MONOXIDE POISONING, AND PROPERTY DAMAGE HAZARD. 

 
Failure to follow this warning could result in death, personal injury, property damage and/or 
equipment damage. 
 
This kit is to be used for terminating condensing Category IV vent furnaces.  DO  NOT use kit 
to terminate Category I, II, or III vent furnaces.

 

 

MG-510   

ECN 5102-MA 091216 

- 1 -

 

Содержание AOPS7488

Страница 1: ...intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments ELECTRIC SHOCK HAZARD FIRE AND OR EXPLOSION HAZARD Failure t...

Страница 2: ...in Cap 3 Rain Cap 2 3 dia x 19 1 2 long SDR 26 pipe 4 dia x 24 long SDR 26 pipe 3 2 dia x 31 5 8 long SDR 26 Pipe 2 1 2 dia x 37 1 8 long SDR 26 pipe 4 2 Wye Fitting 3 Wye Fitting Assembled Concentric...

Страница 3: ...oof termination is preferred since it is less susceptible to damage has reduced intake contaminants and less visible vent vapor For side wall termination consideration should be given to A possible da...

Страница 4: ...ALL INSTALLATIONS AND SERVICE MUST BE PERFORMED BY QUALIFIED SERVICE PERSONNEL VERETICAL TERMINATION HORIZONTAL TERMINATION 4...

Страница 5: ...ALL INSTALLATIONS AND SERVICE MUST BE PERFORMED BY QUALIFIED SERVICE PERSONNEL 2 CONCENTRIC VENT KIT AOPS7488 5...

Страница 6: ...ALL INSTALLATIONS AND SERVICE MUST BE PERFORMED BY QUALIFIED SERVICE PERSONNEL 3 CONCENTRIC VENT KIT AOPS7489 6...

Страница 7: ...r pipe instead of cementing when field disassembly is desired for cleaning see Fig 7 WYE FITTING FIG 5 FIG 6 OUTER PVC PIPE RAIN CAP INNER PVC PIPE APPLY PVC CEMENT THIS END FIG 7 STAINLESS STEEL SCRE...

Страница 8: ...the structure s hole 7 Secure the assembly to the structure as shown in Fig 2 or Fig 3 using field supplied metal strapping or equivalent material NOTE Ensure the termination height is above the roof...

Отзывы: