160
-
'20 • PAC-SM-351
Error code
Remote control:
Content
1-time flash
Keeps flashing
1-time flash
1-time flash
ON
Indoor display
RUN light
TIMER light
Green LED
Yellow LED
Red LED
Outdoor unit
control PCB
Outdoor unit
inverter PCB
E42
Current cut (1/2)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
Power source
voltage OK?
YES
Are the
service valves
opened?
NO
YES
Is the
high pressure
during operation
OK?
YES
Is the
checked result of
insulation resistance and
resistance between terminals (1) of
compressor motor
OK?
YES
(1) 1.044
Ω
or more at 20°C (Models FDC100-140VNX-W)
1.044
Ω
or more at 20°C (Models FDC100-140VSX-W)
NO
NO
NO
To next page.
Check power source.
Open the service valves.
Check refrigerant amount
and refrigerant circuit
* In case of transitional
increase of high pressure
and/or test run, several
times restarting may
recover it, because liquid
refrigerant (migrated)
in the compressor is
discharged from the
compressor.
Replace compressor.
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3.
Condition of error displayed
•
If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
•
After 3-minute delay, the
compressor restarts, but if this
amonaly occurs 4 times within
30 minutes after the intial
detection.
4. Presumable cause
• The service valves closed
• Faulty power source
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note: