106
-
'20 • PAC-SM-351
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
E18
Address setting error of
master and slave indoor units
Keeps flashing 1-time flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
Diagnosis
Countermeasure
• In cases of RC-EX3A
Menu
➞
Service setting
➞
IU settings
➞
Select IU
• In cases of RC-E5
Return address No. to
“IU …” using [
▲
] or
[
▼
] button.
2. Error detection method
IU address has been set using
the “Master IU address set”
function of remote control.
3.
Condition of error displayed
Same as above
4. Presumable cause
Same as above
Note:
Is “Master IU
address set” function of remote
control used?
E18 occurs
YES