'20 • PAC-SM-351
None
Power source system error
(Power source to remote control)
–
–
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is there any
loose connection of remote
control wires?
Is remote
control wire broken or
short-circuited?
Disconnect remote
control wires.
NO
Is DC15V or
higher detected between X-Y
of interface kit terminal
block?
YES
YES
YES
NO
Disconnect
connecting wires.
Is DC15V or
higher detected between X-Y
of indoor unit terminal
block?
YES
NO
NO
Correct.
➞
Insert connector
securely.
Replace wires.
Replace remote control.
Replace interface kit.
Defective indoor unit control
PCB
➞
Replace.
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Remote control wire
breakage/short-circuit
• Defective remote control
• Malfunction by noise
• Broken harness
• Faulty indoor unit control PCB
• Faulty interface kit
Note:
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor unit
control PCB
Content
Содержание SRK100VNXWPZSX
Страница 2: ...1 20 PAC SM 351 TABLE OF CONTENTS 1 HYPER INVERTER PACKAGED AIR CONDITIONERS 2 2 V MULTI SYSTEM 199...
Страница 181: ...180 20 PAC SM 351 1 e SRK series PHA012D402...
Страница 182: ...181 20 PAC SM 351 Screw...
Страница 183: ...182 20 PAC SM 351 3 PHA012D402...
Страница 184: ...183 20 PAC SM 351 4 PHA012D402...